Sensepoint XCD RFD Technical Manual
13.2.1 Configuration mode operation table
Configuration mode allows the user to perform calibration and configure parameters
such as full scale range, calibration gas level, calibration interval, inhibit current &
timeout, alarm settings, relay settings, set a password, etc. To activate Configuration
mode hold the magnet over the ENTER switch for at least 3 seconds and then remove.
Configuration mode can be password protected to prevent unauthorized personnel from
changing parameters. Initially the password is set to '0000' meaning it is disabled. While in
Configuration mode, the output current of the detector is inhibited to prevent false alarms.
Use the table below to help navigate the menus and make configuration changes. The
menus are shown in the left hand column. Use to select the required menu and ''
to enter. Follow the information and instructions in the table from left to right from the
required menu.
OK
GAS NAME, ZERO
CONCENTRATION AND
FLASHING ' ' ICON
SEt
DISPLAYED. APPLY ZERO
CAL
1
GAS AND USE '' WHEN
READING IS STABLE. 'ZEro
PASS' DISPLAYED IF OK,
'ZEro FAIL' IF NOT.
BAR GRAPH INDICATING
CURRENT RANGE, 'rAn9'
SEt
DISPLAYED & CURRENT
rAn9
RANGE FLASHES. USE
TO SELECT DIFFERENT
RANGE
'Inhb' DISPLAYED WITH
'
' ICON FLASHING.
ConF
CURRENT INHIBIT mA
Inhb
VALUE FLASHES. USE
TO SELECT NEW VALUE
'PASS' DISPLAYED WITH
FIRST DIGIT PLACE ICON
OF THE PASSCODE
FLASHING. USE TO
SEt
ST
SELECT 1
PASS
CURRENT PASSWORD.
USE TO MOVE TO NEXT
DIGIT AND SET REST OF
PASSCODE.
'Int' DISPLAYED WITH
CURRENT CALIBRATION
CAL
INTERVAL FLASHING.
2
Int3
USE TO CHANGE
INTERVAL.
OK
'SPAN' DISPLAYED AND
'YES' FLASHING TO
ASK IF YOU NOW WANT
TO PERFORM SPAN
CALIBRATION. USE ''
TO PROCEED OR USE
TO SELECT 'No'
AND RETURN TO MENU
MODE.
IF RANGE IS CHANGED,
'CAL' DISPLAYED AND
'YES' FLASHING TO
ASK IF YOU NOW
WANT TO PERFORM
CALIBRATION. USE ''
TO PROCEED OR USE
TO SELECT 'No'.
'tImE' DISPLAYED WITH
'
' ICON. FLASHING
CURRENT INHIBIT
TIMEOUT PERIOD
(MINUTES) FLASHES.
USE TO SET
NEW TIMEOUT. (IF
SET TO 0 OUTPUT
IS PERMANENTLY
INHIBITED)
UNIT RETURNS TO
DIGIT OF
MENU MODE
'duE' DISPLAYED AND
'No', 'LCd' OR 'ALL'
FLASHING. USE
TO SELECT REQUIRED
CAL DUE WARNING
OUTPUT.
OK
'GAS' TARGET
CONCENTRATION
FLASHING AND ' '
ICON DISPLAYED.
USE TO
CHANGE GAS
CONCENTRATION
AND '' TO START
SPAN CALIBRATION.
IF RANGE IS
CHANGED, 'ALrm'
DISPLAYED AND
'YES' FLASHING TO
ASK IF YOU NOW
WANT TO MODIFY
ALARM SETTINGS.
USE '' TO PROCEED
OR USE TO
SELECT 'No' AND
RETURN TO MENU
MODE.
UNIT RETURNS TO
MENU MODE
UNIT RETURNS TO
MENU MODE
42
SPXCDHMRFEN Issue 4_08-2016
OK
GAS NAME, CURRENT
CONCENTRATION AND
FLASHING ' ' ICON
DISPLAYED. APPLY
SPAN GAS AND USE ''
WHEN READING STABLE.
IF OK 'PASS' & 'PurG'
DISPLAYED (IF FAIL
'SPAN FAIL' DISPLAYED
AND RETURNS TO
MENU). REMOVE SPAN
GAS. WHEN READING
<50% OF SPAN POINT,
COUNTDOWN BEGINS &
UNIT RETURNS TO MENU
MODE.
UNIT RETURNS TO MENU
MODE