4.2 Service Menu - Viessmann Vitoflex RF 150 Installation And Service Instructions Manual

Wood-fired boiler, output range: 154/205/273/341/478-512/751/1024/1365/1843 mbh, 45/60/80/100/140-150/220/300/400/540 kw
Table of Contents

Advertisement

Operation
ECOTRONIC Control System

4.2 Service Menu

Menu designation: - Vitoflex 300-RF service
Access menu:
- Hold down O, press F3 briefly
Exit menu:
- Press F3 briefly or automatically after 60 seconds
Note: Depending on the design and setting, some menus and text do not appear.
Screen number Screen text
(1)
Customer details
(2)
Boiler data
(3)
Boiler valve actuating drive
Operating time
(7)
Flue gas blower with
oil/gas-fired operation
Nominal RPM
(Not applicable to North
America)
(11)
System target
temperature minimum
(18)
Oil/gas burner
on the Vitoflex 300-RF
ECO
(20)
Flue gas recirculation
system
(30)
Output controller factor
(31)
Material volume
controller factor
(33)
Boiler inlet
Maximum
(34)
Boiler inlet
Maximum
delay
(37)
In-feed auger
Terminate idle time at
(38)
In-feed auger
tube temperature
limit value
(40)
Ember monitoring system
level
58
(continued)
Parameter description
Display customer details and software version
Display all boiler target values
Operating time of the boiler control valve actuating drive
SQS35.00 and SQY31  operating time 120 seconds
Speed of flue gas blower on the Vitoflex 300-RF ECO.
The speed of the flue gas exhaust blower can be
adjusted between 0 and 60 Hz in 14 levels.
Only display if:
oil/bas burner available (Service Vitoflex 300-RF)
Is a minimum threshold of the system target temperature
necessary (e.g. with customer-side heat distribution this
parameter must be set to Yes)?
It is possible to adjust the minimum target system
temperature in the parameters menu
Is an oil/gas burner fitted to the Vitoflex 300-RF ECO
Is a flue gas recirculation system installed?
(Flue gas recirculation system YES: the primary air
vent is closed below 30 Hz depending on the current
speed of the flue gas blower in order to feed more
recirculated flue gas to the combustion in lower partial
load operation)
Speed of the output controller:
 Rotational speed increase or decrease
Speed of the material volume controller
 In-feed auger duty cycle
Vitoflex 300-RF maximum supply temperature:
when this temperature is exceeded the system switches
from load operation to auger idle run.
Time delay on exceeding the maximum supply
temperature  empty auger.
On loader idle run, the in-feed auger is halted if the
residual oxygen content exceeds this limit value 
IMPORTANT: Noise development from the empty in-feed
auger!
When this limit value is exceeded the in-feed auger is run
idle in automatic mode
( In-feed auger warm)
At which light barrier should the ember monitoring
system initiate control:
Large ember bed: both light barriers must be broken.
Small ember bed: only light barrier 1 (closer to the in-
feed and /or lower) must be broken
Vitoflex 300-RF Installation & Operating
Factory setting
-
-
140 sec
4
No
No
No
10
25
194°F
(90°C)
60 sec
16.0%
158°F
(70°C)
Large ember
bed