Viessmann Vitoflex RF 150 Installation And Service Instructions Manual page 62

Wood-fired boiler, output range: 154/205/273/341/478-512/751/1024/1365/1843 mbh, 45/60/80/100/140-150/220/300/400/540 kw
Table of Contents

Advertisement

Operation
ECOTRONIC Control System
5.2 Loading Service Menu (continued)
Screen number Screen text
(6)
Feed system 1
.........
light barrier
delay
(7)
Feed system 2
to
to conveying
(22)
equipment 15
light barrier delay
(30)
Extraction system 1
....
preferred direction
(31)
Extraction system 1
.....
reversing interval
(33)
Extraction system 1
cross load module
light barrier delay
(34)
Extraction system 1
cross load module
maximum operating
time
(35)
Extraction system 1
Hydraulics
pulse
(40)
Extraction system 2
......
Preferred direction
62
(continued)
Parameter description
Delay of the conveying equipment 1 light barrier
(e.g. in-feed auger 1)
Only display if:
Conveying equipment 1 available with light barrier
Delay of the conveying equipment 2 to 15 light barriers
Only display if:
Conveying equipment available with light barriers
Extraction system 1 with preferred rotating direction
available?
Only display if:
Extraction system with reversing (funnel extraction system)
Reversing interval extraction system 1
Preferred direction YES: The extraction is reversed in
the event of an overload (current measurement) for the
duration of the reversing interval. Subsequently preferred
direction of rotation.
Preferred direction NO: Extraction is reversed in the
event of an overload (current measurement) and after the
duration of the reversing interval.
Only display if:
Extraction system with reversing
(funnel extraction system)
Delay of the light barrier walking floor auger extraction
system 1
Only display if:
Extraction system 1 hydraulic extraction system available
Maximum operating time of the walking floor auger
extraction system 1 with walking floor auger light barrier
broken  forced control hydraulic drive
Only display if:
Extraction system 1 hydraulic extraction system available
Following expiration of the maximum operating time of the
walking floor auger extraction system 1 with broken light
barrier of the walking floor auger, the hydraulic unit is
force-controlled for this pulse time.
Only display if:
Extraction system 1 hydraulic extraction system available
Extraction system 2 with preferred rotating direction
available?
Only display if:
Extraction system with reversing (funnel extraction system)
Vitoflex 300-RF Installation & Operating
Factory setting
500 ms
500 ms
No
240 sec
2500
ms
80 sec
20 sec
No

Advertisement