3.5 Registering WinCC tags in the WinCC Data Manager

3.5
Registering WinCC tags in the WinCC Data Manager
Introduction
All tags that are configured in WinCC for data exchange between the "FB_UA_RM" and
"FB_UA_WM" blocks and the OS must be registered in the WinCC Data Manager. For this,
the tags must be entered as a trigger in the "FB_RawDataTrigger.pas" action.
Requirement
● WinCC Explorer is open.
Procedure
To enter a tag as a trigger, follow these steps:
1. Open the "FB_RawDataTrigger.pas" action in the Global Script Editor.
2. Click the
The "Properties" dialog box opens.
3. Open the "Trigger" tab.
4. Select the "Tag" entry and click the "Add" button.
The "Add trigger" dialog box opens.
5. Use the
"FB_UA_RM" and "FB_UA_WM" blocks. See section Creating raw data tags in WinCC
(Page 23).
6. Click "OK".
26
button in the toolbar.
button in the "Tag name" area to insert the tags that you configured for the
Advanced Process Functions Engineering Manual