Configuring AS-OS communication
3.4 Creating raw data tags in WinCC
7. In the "R_ID" field, enter the value that you have configured for the "R_ID1" input parameter
of the associated "FB_UA_RM" function block.
8. Select the "BSEND/BRCV" option.
9. Close the dialog box by clicking "OK".
User Archive Write Manager
To create the tags for data exchange with the "FB_UA_WM" block, follow these steps:
1. Open the configured communication connection in the WinCC Explorer Tag Management
(you can find it with the S7 program name under "Named Connections"). See section Setting
up an S7 connection (Page 13).
2. Enter a new tag at the end of the tag list.
3. Enter the tag name according to the following pattern:
The "Name of CFC" prefix refers to the name of the CFC in which the "FB_UA_WM" function
block is configured and to which a connection must be established.
The name "UA_WM_DATA" is specified by the APF system and must also not be changed
here or in subsequent configuring steps.
Example:
If the CFC is called "FB_UA_WM", the tag name is: FB_UA_WM/UA_WM_DATA.
4. In the "data type" column, select the entry "raw data type".
5. Click the "...." button in the "Address" column. The "Address Properties" dialog opens.
6. Select the "Raw data" check box.
24
Name of CFC/UA_WM_DATA
Advanced Process Functions Engineering Manual