Viessmann Vitodens 200 Service Instructions Manual page 82

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Troubleshooting
Repairs
(cont.)
Checking the temperature limiter
If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 75 °C, check the following:
1. Pull the leads from thermocouple
A.
82
2. Check the continuity of the thermo-
couple with a multimeter.
3. Remove the faulty thermocouple.
4. Install a new thermocouple.
5. After commissioning, press reset
button "E" at the control unit.