Repairs
(cont.)
Checking the boiler water temperature sensor, cylinder tem-
perature sensor or the flow temperature sensor for a low loss
header
1.
Boiler water temperature sensor:
Pull the leads from boiler water
temperature sensor A and
check the resistance.
Cylinder temperature sensor: Pull
plug % from the cable harness at
the control unit and check the
resistance.
Flow temperature sensor: Pull
plug "X3" from the control unit
and check the resistance across
terminals "X3.4" and "X3.5".
Troubleshooting
79