Viessmann Vitodens 200 Service Instructions Manual page 71

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Fault codes
(cont.)
Display
Const.
Weath.-
fault
comp.
code
9F
X
X
A7
X
b0
X
X
b1
X
X
b4
X
X
b5
X
X
b7
X
X
b8
X
X
System char-
Cause
acteristics
Control mode
Solar control
unit fault;
displayed if a
fault without
fault code
occurs at the
solar control
unit
Control mode
Faulty pro-
as per the de-
gramming
livered condi-
unit
tion
Burner
Flue gas
blocked
temperature
sensor
shorted out
Control mode
Communica-
as per the de-
tion error;
livered condi-
program-
tion
ming unit (in-
ternal)
Regulates as
Internal fault
if the outside
temperature
was 0 °C
Control mode
Internal fault
as per the de-
livered condi-
tion
Burner
Boiler coding
blocked
card miss-
ing, faulty or
incorrect
boiler coding
card
Burner
Flue gas
blocked
temperature
sensor lead
broken
Troubleshooting
Measures
Check the solar
control unit (see
solar control unit
service instruc-
tions).
Replace the pro-
gramming unit.
Check the flue
gas temperature
sensor (see page
80).
Check connec-
tions and replace
the programming
unit if required.
Replace the con-
trol unit.
Replace the con-
trol unit.
Plug in boiler cod-
ing card or re-
place it, if faulty.
Check the flue
gas temperature
sensor (see page
80).
71