Viessmann Vitodens 200 Service Instructions Manual page 46

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
73:0
DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
General
76:0
Without LON communi-
cation module (only for
weather-compensated
control units)
77 :1
LON user number (only
for weather-compen-
sated control units)
79:1
With LON communica-
tion module: The control
unit is fault manager
(only for weather-com-
pensated control units)
7b:1
With LON communica-
tion module: The control
unit transmits the time
(only for weather-com-
pensated control units)
7F:1
Detached house (only
for weather-compen-
sated control units)
80:1
A fault message is dis-
played, providing a fault
is active for at least 5 s
46
Possible change
73:1
During the time program
to
1x/h "ON" for 5 min
73:6
up to 6x/h "ON" for 5 min
73:7
Permanently "ON"
76:1
With LON communication
module; automatic recog-
nition
77 :2
LON user number, adjus-
to
table from 1 to 99:
77 :99
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 050
99 = Vitocom
Note
Allocate each number
only once.
79:0
Control unit is not fault
manager
7b:0
Do not transmit time
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heat-
ing, as option
80:0
Immediate fault message
80:2
The fault message is is-
to
sued after a delay, which
80:199
is adjustable from 10 s to
995 s; 1 step = 5 s