Viessmann Vitodens 200 Service Instructions Manual page 73

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Fault codes
(cont.)
Display
Const.
Weath.-
fault
comp.
code
C6
X
C7
X
X
Cd
X
X
CE
X
X
CF
X
dA
X
System char-
Cause
acteristics
Control mode,
Communica-
max. pump
tion fault -
speed
external vari-
able speed
heating cir-
cuit pump,
heating cir-
cuit with
mixer M2
Control mode,
Communica-
max. pump
tion fault -
speed
external vari-
able speed
heating cir-
cuit pump,
heating
circuit A1
Control mode
Communica-
tion fault
Vitocom 100
(KM BUS)
Control mode
Communica-
tion fault -
ext. exten-
sion
Control mode
Communica-
tion fault -
LON com-
munication
module
Control mode
Room tem-
without room
perature
influence
sensor, heat-
ing circuit A1
shorted out
Troubleshooting
Measures
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: OFF
Switch 2: ON
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring box:
Switch 1: ON
Switch 2: OFF
Check connec-
tions, Vitocom 100
and coding ad-
dress "95".
Check connec-
tions and coding
address "2E".
Replace the LON
communication
module.
Check the room
temperature sen-
sor, heating cir-
cuit A1.
73