Viessmann Vitodens 200 Service Instructions Manual page 36

Type wb2a, 8.8 to 20.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Hide thumbs Also See for Vitodens 200:
Table of Contents

Advertisement

Coding
Code 1
(cont.)
Overview
Coding
Coding in the delivered condition
System design
00 :1
System version 1:
1 heating circuit without
mixer A1, without DHW
heating
Max. boiler temp.
06:...
Maximum limit of the
boiler water tempera-
ture, defaulted by the
boiler coding card
Gas type
1E:0
Operation with natural
gas
Venting/filling
2F:0
Venting program/filling
program disabled
36
Possible change
00 :2
System version 1:
1 heating circuit without
mixer A1, with DHW heat-
ing
00 :3
System version 4:
1 heating circuit with
mixer M2, without DHW
heating
00 :4
System version 4:
1 heating circuit with
mixer M2, with DHW
heating
00 :5
System version 2, 3:
1 heating circuit without
mixer A1 and 1 heating
circuit with mixer M2,
without DHW heating
00 :6
System version 2, 3:
1 heating circuit without
mixer A1; 1 heating cir-
cuit with mixer M2, with
DHW heating
06:20
Maximum limit of the boil-
to
er water temperature
06:127
within the ranges de-
faulted by the boiler
1E:1
Operation with LPG
2F:1
Venting program enabled
2F:2
Filling program enabled