Fujitsu Waterstage WS G140DC6 Series Maintenance Document page 60

Air to water heat pump. split system (single phase type). split system (3-phase type).
Table of Contents

Advertisement

Split system (Single phase and 3-phase type)
Reduced Setpoint Increase
Line no.
HC1
HC2
800
1100
801
1101
This function is used mainly in heating installations
that do not have high supplies of power (e.g. low
energy
homes).
In
temperatures are low, adjusting the temperature
would be too long.
Comfort
setpoint(710)
Reduced
setpoint(712)
Mixing Valve Control
Line no.
HC1
HC2
830
1130
834
1134
Mixer valve boost
The controller adds the increase set here to the
current flow setpoint and uses the result as the
temperature setpoint for the heat generator.
Controlled floor drying function
Line no.
HC1
HC2
850
1150
851
1151
856
1156
857
1157
This function is used in the controlled drying of floors.
It adjusts the flow temperature to a temperature
profile. Drying is performed by floor heating via the
heating circuit with a mixing valve or with a pump.
Floor curing function
Off:
The function is deactivated.
Heating operational (Fh):
The
first
part
of
automatically completed.
Heating "ready for occupancy" (Bh)
60
Programming line
Reduced setpoint increase start
Reduced setpoint increase end
that
case,
when
Begin
increase(800)
Programming line
Mixer valve boost
Actuator running time
Programming line
Floor curing function
Floor curing setpoint manually
Floor curing day current
Floor curing day completed
the
temperature
profile
Increasing the reduced setpoint prevents excessive
cooling of the rooms in order to shorten the
outdoor
temperature adjustment period when changing over
to the comfort setpoint.
End increase
(801)
Averaged OT
Actuator running time
For 3-position control the valve Actuator running time
can be adjusted. With a 2-position servomotor, the
adjusted travel time is inoperative.
The second part of the temperature profile is handled
automatically..
Heating "ready for occupancy" / Heating
operational
The full temperature profile (1st and 2nd part) is
performed automatically.
Manual
No temperature profile is performed, but the control is
performed according to the "manual controlled drying
setpoint". The function is automatically terminated
is
after 25 days
Maintenance Document 1544-1