Fujitsu Waterstage WS G140DC6 Series Maintenance Document page 14

Air to water heat pump. split system (single phase type). split system (3-phase type).
Table of Contents

Advertisement

Split system (Single phase and 3-phase type)
Clear 8: Heat-exchange thermistor (outlet) error :
Hydraulic Unit LED: Green 7 flashes / Red 3 flashes
Outdoor Unit LED: 4 flashes
Probable causes:
Misconnection.
Sensor fault.
Main PCB failure.
Check:
1. Check the sensor connection:
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
-
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistancer value
Temperature (°C)
Resistance (kΩ)
27,5 20,9 16,1 12,4 9,73 7,67 6,1 3,95
- If the thermistor is faulty, replace it.
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC5.0V)
THERMISTOR
(COMPRESSOR)
THERMISTOR
(OUTDOOR)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(HEAT SINK)
THERMISTOR
(PIPE MID)
THERMISTOR
(EXPANSION)
- If there is no voltage, replace Main PCB.
14
OK
-10
-5
0
10
OK
15
20
25
30
Maintenance Document 1544-1