Fujitsu Waterstage WS G140DC6 Series Maintenance Document page 77

Air to water heat pump. split system (single phase type). split system (3-phase type).
Table of Contents

Advertisement

Split system (Single phase and 3-phase type)
Basic unit EX/E
Line no.
Programming line
5981
Cont type input EX1, EX2, EX3
5983
5985
The type of contact can be selected:
NC
The input's function is active when voltage is not
present.
Sensor Corrections
Line no.
Programming line
6098
Not used
6100
Readjustm outside sensor
The outdoor temperature measuring value can be
corrected within a range of +/- 3 K.
Installation Frost Protection
Line no.
Programming line
6120
Frost protection plant
According to the outdoor temperature, the heating
circuit pump and the condenser pump are switched
on although there is no demand for heat
Miscellaneous
Line no.
Programming line
6205
Reset to default parameters
6220
Software version
Reset to default parameters :
All parameters can be reset to factory settings,
except when it comes to the following pages: Time
and date, User interface and all time programs, as
well as the operating hours and the various counters.
Maintenance Document 1544-1
Outdoor
Pump
temperature
Continuously ON
Set to ON for 10 min, approx. every
6 hours.
Continuously off
NO
The input's function is active when voltage is present.
The descriptions relating to the functions of the EX
contact apply when an NO contact is selected.
Diagram
ON
Periodically ON
OFF
Software version:
The software version represents the controller
software status at the time the unit is being produced.
It is printed on the back of the unit.
The first two digits represent the software version,
and the third is the revision number (e.g. 01.0)
77