Siemens SIPLUS RIC IEC on S7 Manual page 26

Addon nodal blocks version v1.5
Table of Contents

Advertisement

Structure and values of the (optional) parameter data block for IOA conversion:
The use of this parameter DB should be carried out, when only specific information object addresses shall
be processed or must be converted.
The parameter DB has the following structure:
Group /
Parameter
DB_Manag
DB_Manag.
Pos_of_DB
DB_Manag.
No_of_all_DBs
DB_Manag.
DB_No_Act
DB_Manag.
DB_No_Prev
DB_Manag.
DB_No_Next
DB_Manag.
Reserved
Info_Manag
Info_Manag.
P_Byte_First_Info
Info_Manag.
No_of_Infos
Info_Manag.
Len_Info
Info_Manag.
Len_Sort_Key
DB_Manag.
Re_internal_usage
Global
Global.
Para_DB_Type
Global.
Int_W22
IEC_Addr
IEC_Addr.
P_Src_Info_Address
IEC_Addr.
P_Dst_Info_Address
These values are pre-adjusted in the sample DB (DB166) and have not to be changed.
Note:
Changes have to be performed always in the ‚Data view', and not in the ‚Declaration view'
(except dimensioning of the array).
SIPLUS RIC IEC on S7 V1.5
Functional description
Addr.
Addr.
Type
rel
Abs
0
0
STRUCT
+0.0
0.0
BYTE
+1.0
1.0
BYTE
+2.0
2.0
WORD
+4.0
4.0
WORD
+6.0
6.0
WORD
+8.0
8.0
WORD
+10.0
10.0
END_STRUCT
STRUCT
+0.0
10.0
+2.0
12.0
+4.0
14.0
BYTE
+5.0
15.0
BYTE
+6.0
16.0
DWORD
+10.0
20.0
END_STRUCT
STRUCT
0.0
20.0
WORD
2.0
22.0
WORD
+4.0
24.0
END_STRUCT
ARRAY [1..n]
STRUCT
+0.0
24.0
+4.0
28.0
DIN T
+8.0
32.0
END_STRUCT
!!! These values are parameter and can be adjusted !!!
Page 26 of 28
Start value
B#16#0
B#16#0
W#16#0
W#16#0
W#16#0
W#16#0
INT
24
INT
0
B#16#8
B#16#0
DW#16#0
W#16#A601
W#16#0
DINT
L#0
B#16#0
Comment
reserved for future - do not change !
reserved for future - do not change !
reserved for future - do not change !
reserved for future - do not change !
reserved for future - do not change !
reserved for future - do not change !
END_STRUCT (10 BYTE)
(Byte-) Position of first Para-Block - do
not change !
0:unspecified (DB is filled up to the end);
otherwise size n of ARRAY [1..n]
Difference in [byte] between two Para-
Blocks - do not change !
0: without sorting; > 0: Data sets are sort-
ed ascending with x Bytes
END_STRUCT (10 BYTE)
Internal identifier for this Data Block - do
not change
Reserved for internal use
END_STRUCT (4 BYTE)
n = Anzahl Parametereinträge
IOA Information object address from
T101 / T104 (Source)
IOA to T101 / T104 (Destination): 0: IOA
from Src will be used.
END_STRUCT (8 BYTE)
©SIEMENS AG 2013
I IA CE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents