Nodal Block Slomai_Cd_Pdb (Fb166) - Siemens SIPLUS RIC IEC on S7 Manual

Addon nodal blocks version v1.5
Table of Contents

Advertisement

3.1.2.1. Nodal block SLoMAi_CD_pDB (FB166)

The block receives single, double or tap changing commands as well as analog and digital setpoint val-
ues from the control center and transfers these to the subordinated remote control unit.
Illustration as CFC-block with default values
Important features are:
 With minor effort of parameterization you can process all information in command direction:
- Single commands with TK 45, 58
- Double commands with TK 46, 59
- Tap changing commands with TK 47, 60
- Setpoint command with normalized value with TK 48, 61
- Setpoint command with scaled value with TK 49, 62
- Setpoint command with shortened floating point number with TK 50, 63
- Digital setpoint commands with 32 Bit bit pattern with TK 51, 64
 Readings for the default adjustments can be taken from the corresponding variable comment.
On the other hand only a minimum of mandatory inputs are required.
The interconnection of ‚P_Application_Src', ‚ASDU_Adr_Src', ‚P_Application_Dst' and ‚AS-
DU_Adr_Dst' is a minimum requirement.
 Possibility for filtering by
- defined address bands with ‚First_Info_Adr_Src', ‚Last_Info_Adr_Src'
 Parameterization of the information object addresses (IOA) to be transferred not necessary if
the addresses can be used 1:1.
 The allocation of an optional parameter data block enables the conversion of the information ob-
ject addresses.
 A global blocking input allows the easy locking of all commands
Output for external evaluation of an active input command existing
Function (output) independent from received TK
 Command storage and serial output of the buffered commands possible
(number according to ‚Cmd_Buffer_Dim)
SIPLUS RIC IEC on S7 V1.5
Functional description
CALL
Comp_ID
P_Application_Src
ASDU_Adr_Src
First_IOA_or_Para_DB_No:=L#1
Last_IOA_or_No_of_Infos:=L#8
P_Application_Dst
ASDU_Adr_Dst
Lock
With_Termination
Timeout_Conf
Timeout_Term
Cmd_Buffer_Dim
CMD_RUN
CMD_Buf_DB
Illustration in AWL with fractional parameter supply
Page 23 of 28
"SLoMAi_CD_pDB" , DB201
:=B#16#41
:=#P_Appl_Sl
:=L#21
:=#P_Appl_Ma
:=L#5
:=
:=
:=
:=T#5S
:=
:=M400.0
:=
©SIEMENS AG 2013
I IA CE

Hide quick links: