Part name
No.
Heat
⑨
1. Detachment
exchanger
1) Recover the refrigerant gas and then remove
the refrigerant pipe of the indoor unit.
2) Perform 1 of ⑦ to remove the drain pan.
3) Remove the screw A (M4 x 0.4" (10mm), 7 pcs)
and remove the Left side panel.
4) After performing 1) and 3) of 1 of ⑧ ,
withdraw the wire of the sensor from the
bushing to the heat exchanger side.
5) Remove the screw B (M4 x 0.4" (10mm), 3 pcs)
and remove the evaporator partition (back).
6) Remove the screw C (M4 x 0.4" (10mm), 4 pcs)
and remove the evaporator partition (down).
7) Remove the screw D (M4 x 0.4" (10mm), 5 pcs)
of the right side panel.
8) While holding the heat exchanger, remove the
screw E (M4 x 0.4" (10mm), 2 pcs) and then
take out the heat exchanger slowly.
Screw E
2. Attachment
Attach the heat exchanger to the original position.
1)
Screw E (M4 x 0.4" (10mm), 2 pcs)
Fix the screw D on the right side panel as before.
2)
Screw D (M4 x 0.4" (10mm), 5 pcs)
Attach the evaporator partition (down) as before.
3)
Screw C (M4 x0.4" (10mm), 4 pcs)
Attach the evaporator partition (back) as before.
4)
Screw B (M4 x 0.4" (10mm), 3 pcs)
Perform 1) , 3) and 4) of 2 of ⑧ to attach the
5)
sensor conector and electrical parts box cover .
Attach the Left side panel as before.
6)
Screw A (M4 x 0.4" (10mm), 7 pcs)
Perform 2 of ⑦ to attach the drain pan and
7)
bottom plate (drain side).
Procedure
Screw C
Evaporator partition
(down)
- 94 -
Remarks
Heat exchanger
Left side panel
Screw A
Right side panel
screw D
Bushing
Screw B
Evaporator partition (back
Screw E