9-1-5. Monitor Function of Remote Controller
Calling of sensor temperature display
<Contents>
Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by
calling the service monitor mode from the remote controller.
<Procedure>
1
TEST
CL
Push
+
buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the master indoor unit No. is
displayed, at first and then the temperature of CODE No.
displayed.
2
Push temperature set
the CODE No. of data to be monitored.
The item code list is shown below:
CODE No.
Data name
01
Room temperature
(Remote controller)
02
Indoor suction temperature (TA)
03
Indoor heat exchanger (Coil)
temperature (TCJ)
04
Indoor heat exchanger (Coil)
temperature (TC)
Indoor fan revolution frequency
07
F2
Indoor fan calculated operation time
F3
Filter sign time
3
UNIT LOUVER
Push
button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
4
TEST
Pushing
button returns the status to the usual display.
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.
• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73] are
not displayed.
TEMP.
buttons and then change
Unit
°C
°C
°C
°C
rpm
×100h
×1h
- 76 -
00 00 00 00 00
is
FILTER
RESET
2
<Operation procedure>
1
CODE No.
Data name
60
Outdoor heat exchanger (Coil) temperature (TE)
61
Outside temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
Heat sink temperature (THS)
6A
Operation current (× 1/10)
6D
Outdoor heat exchanger (Coil) temperature (TL)
70
Compressor operation frequency
72
Outdoor fan revolution frequency (Lower)
73
Outdoor fan revolution frequency (Upper)
F1
Compressor calculated operation time
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
A A
VENT
L L
TEST
SET
CL
SWING/FIX
UNIT LOUVER
T
4
1
3
2
3
4
Returned to usual display
×100h
Unit
°C
°C
°C
°C
°C
A
°C
rps
rpm
rpm