10-3. Address Setup (Manual Setting from Remote Controller)

In case that addresses of the indoor units will be
determined prior to piping work after cabling work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
SET
CL
TEST
Push
+
+
for 4 seconds or more.
2
(← ← ← ← ← Line address)
Using the temperature setup
12
set
to the CODE No.
3
Using timer time
4
SET
Push
button. (OK when display goes on.)
5
(← ← ← ← ← Indoor unit address)
Using the temperature setup
6
Using timer time
7
SET
Push
button. (OK when display goes on.)
8
(← ← ← ← ← Group address)
Using the temperature setup
9
Using timer time
10
SET
Push
button. (OK when display goes on.)
11
TEST
Push
button.
Setup completes. (The status returns to the usual stop status.)
2, 5, 8
END
<Operation procedure>
1
2
buttons simultaneously
/
buttons,
/
buttons, set the line address.
/
buttons, set
/
buttons, set 1 to the line address.
/
buttons, set
0000
/
buttons, set
TEMP.
11
FILTER
L L
RESET
TEST
1
3
4
5
6
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
Outdoor
Indoor
Line address → 1
Indoor unit address → 1
Group address → 1
Remote controller
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit cable.
Group address
Individual
Header unit : 0001
Follower unit : 0002
13
to the CODE No.
14
to the CODE No.
0001
to Individual,
to Master unit, and
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
A A
VENT
SET
CL
SWING/FIX
UNIT LOUVER
T
7
8
9
- 86 -
Outdoor
1 2 3
1 2 3
1 2 3
1 2 3
Indoor
A B
A B
2
1
2
A B
: 0000
In case of group control
0002
to sub unit.
3, 6, 9
4, 7, 10
10
11
END