Installation and Operating Instructions
UK
NOTE
CHAPTER 5
TECHNICAL DATA
Bearing Condition Diagnostic System LZD ...
4.5
Connection to the computer
Fig.5
Interface converter
Unit 1
Max. 247 units
Unit 247
– RS485 data cable (max. length 400 m)
2
Min. 0.5 mm
per wire (twisted pair) - shielded by additional shielded conductor (to carry to ground)
Observe the generally applicable installation instructions for RS485 networks!
5.0
Technical data
Power supply
Power consumption
In- and outputs
Stand-alone solution
Connection via
USB interface converter
Integration in building
management system
Protection type
Protection class
Environmental conditions
Temperature
Storage temperature
System requirements
of fans concerning
mains power supply
Casing
or integration in the building management system (BMS)
Accessories
including USB cable
230V, 1~, 50 Hz
5 W
3x LED for operating and error display
Modbus RTU
RS485 (communication and programming interface)
1 unit
37 units
247 units
IP 67 (pursuant to DIN EN 60529) using proper fittings
II
Usage for outdoor installation (UV-resistant)
-30 °C ... +50 °C (operating temperature)
-30 °C ... +70 °C
no inverter operation!
Type PCI – compact casing with transparent cover
Installation on a flat surface --> Holder on fan
8
Integration in BMS
Unit 1
Max. 247 units
Unit 247
BMS