Installation and operating instructions
sensor for schools (CO2 Monitor ) with traffic light indicator and acoustic signal, incl. power supply unit,
Maintenance-free CO
2
self-calibrating, in an elegant plastic housing, for determining the CO
ducer converts the measurand to a standard signal, which is directly presented visually by five coloured LEDs (traffic light indica-
tor). An additional signal tone sounds when the warning levels are reached (can be switched on via DIP switch). Available in device
versions CO2 AP for direct wall mounting, CO2 UP for mounting on in-wall flush boxes and CO2 AP-A as a floor-mounted device
with a metal support.
The room sensor is used in classrooms, training rooms and convention centres, offices, hotels, apartments, shops, etc. and is
used for easy and quick evaluation of the indoor climate. This enables energy-saving room ventilation on an as-needed basis, and
improving well-being. The CO

TECHNICAL DATA

Power supply:
Electrical connection:
Sensor:
Measurement range:
Measuring accuracy:
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
Ambient temperature:
Warm-up time:
Housing:
Dimensions:
Installation:
Protection class:
IP rating:
Standards:
Equipment:
CO2 Monitor
measurement is performed using an optical NDIR sensor (non-dispersive infra-red technology).
2
CO2 UP:
5...24 V DC /230 V AC (power supply unit)
CO2 AP:
5...24 V DC /230 V AC (power supply unit)
CO2 AP-A:
5 V DC
CO2 UP:
terminal srews on circuit board (0.14 - 1.5 mm²), in-wall power supply unit (open
cable ends)
CO2 AP:
terminal srews on circuit board (0.14 - 1.5 mm²), plug-in power supply unit
(open cable ends/Euro plug)
CO2 AP-A:
Micro-USB socket on circuit board,
Micro-USB power supply (micro-USB/Euro plug)
optical NDIR sensor (non-dispersive infrared technology),
with manual calibration (via zero button) with automatic calibration
0...3000 ppm
typically ± 30 ppm ± 3% of measured value
± 5 ppm ⁄ °C or ± 0.5% of measured value ⁄ °C (whichever is greater)
± 0.13% ⁄ mm Hg
< 2% in 15 years
by diffusion
0...+ 50 °C
approx. 1 hour
plastic, material ABS, colour pure white (similar to RAL 9010)
85 x 85 x 27 mm
CO2 UP, CO2 AP: wall mounting or on in-wall flush box, Ø 55 mm, base with 4-hole for mounting
on vertically or horizontally installed in-wall flush boxes for cable entry from the back, with pre-
determined breaking point for on-wall cable entry from top ⁄ bottom in case of plain on-wall
installation
CO2 AP-A: mobile CO
2
III (according to EN 60 730)
IP 30 (according to EN 60 529)
CE-conformity, electromagnetic compatibility
according to EN 61 326, EMC directive 2014 ⁄ 30 ⁄ EU,
low voltage directive 2014 ⁄ 35 ⁄ EU
traffic light indicator (five coloured LEDs, see table)
acoustic signal (signal can be switched on) for displaying the CO
Type-specific equipment (see table):
content of room air (0...3000 ppm). The measuring trans-
2
/230 V AC (power supply unit)
measuring instrument on stand holder (table-top unit)
7
concentration
2

Advertisement