Menu 21: Operating Parameters For A Second Motor; List Of Parameters In Menu 21 - Emerson Commander SX Advanced User's Manual

Ip66/nema 4x variable speed drive
Table of Contents

Advertisement

CONTROL TECHNIQUES

MENU 21: OPERATING PARAMETERS FOR A SECOND MOTOR

20 - MENU 21: OPERATING PARAMETERS FOR A SECOND MOTOR

20.1 - List of parameters in Menu 21

Parameter
21.01
Motor 2 maximum reference clamp
21.02
Motor 2 minimum reference clamp
21.03
Motor 2 reference selector
21.04
Motor 2 acceleration rate
21.05
Motor 2 deceleration rate
21.06
Motor 2 rated frequency
21.07
Motor 2 rated current
21.08
Motor 2 rated speed
21.09
Motor 2 rated voltage
21.10
Motor 2 rated power factor (cos ϕ)
21.11
Motor 2 number of poles
21.12
Motor 2 stator resistance
21.13
Motor 2 voltage offset
21.14
Motor 2 inductance
21.15
Motor 2 parameters active
21.16
to
Not used
21.23
21.24
Motor 2 stator inductance L
21.25
to
Not used
21.29
21.30
Motor volts per 1000 rpm (Ke)
21.31
to
Not used
21.50
21.51
q axis inductance
: Function not available.
ADVANCED USER GUIDE
Commander SX
IP66/Nema 4X variable speed drive
Name
S
Type
Adjustment range
R-W
0 to 32000 rpm
R-W/P
0 to 32000 rpm
R-W
0 to 4
R-W
0 to 600.0 s/1000 rpm
R-W
0 to 600.0 s/1000 rpm
R-W
0 to 400.0 Hz
0 to drive rated current
R-W
(A)
R-W
0 to 9999 rpm
R-W
0 to 480 V
R-W
0 to 1.00
R-W
0 to 4
0 to 32.000 Ω
R-W
RO
0 to 25.5 V
R-W
0 to 3200.0 mH
RO/P
0 or 1
R-W
0 to 3200.0 mH
R-W
0 to 10000 V
R-W
0 to 999.9 mH
3854 en - 03.2008 / b
User
Factory setting
setting
Eur: 1500 rpm
USA: 1800 rpm
0
0
3.0 s/1000 rpm
5.0 s/1000 rpm
Eur: 50.0 Hz
USA: 60.0 Hz
Motor rated
current (A)
corresponding to
the drive rating
Motor rated speed
(rpm)
corresponding to
the drive rating
Eur L: 200 V
USA L: 230 V
Eur H: 400 V
USA H: 460 V
0.85
0
0
-
0
-
150.0 mH
98 V
150.0 mH
129