Explanation Of Parameters In Menu 16 - Emerson Commander SX Advanced User's Manual

Ip66/nema 4x variable speed drive
Table of Contents

Advertisement

CONTROL TECHNIQUES
18.3 - Explanation of parameters in
menu 16
16.01
: Timer 1 output
16.11
: Timer 2 output
16.21
: Timer 3 output
16.31
: Timer 4 output
Adjustment range : 0 or 1
0 (Disabled) (OFF)
1 (Enabled) (On)
These parameters indicate the state of the timer relay
outputs.
16.02
: Timer 1 source
16.12
: Timer 2 source
16.22
: Timer 3 source
16.32
: Timer 4 source
Adjustment range : 0.00 to 21.51
: 0.00
Factory setting
These parameters are used to select the source for the timer
relay inputs.
Only "bit" type parameters can be assigned to these inputs. If
an unsuitable parameter is addressed on an input, the input
will be frozen at 0.
16.03
: Timer 1 mode select
16.13
: Timer 2 mode select
16.23
: Timer 3 mode select
16.33
: Timer 4 mode select
Adjustment range : 0 or 1
Factory setting
: 0
0 (ON timer) (On): The relay is used for on-delay timing.
The output changing to 1 is delayed in relation to the
input changing to 1.
1 (OFF timer) (OFF): The relay is used for off-delay timing.
The output changing to 0 is delayed in relation to the input
changing to 0.
16.04
: Timer 1 unit
16.14
: Timer 2 unit
16.24
: Timer 3 unit
16.34
: Timer 4 unit
Adjustment range : 0 to 2
Factory setting
: 0
0 (Second) (Sec): The unit of time for the timer relay is the
second.
1 (Minute) (Min): The unit of time for the timer relay is the
minute.
2 (Hour) (hour): The unit of time for the timer relay is the
hour.
124
ADVANCED USER GUIDE
Commander SX
IP66/Nema 4X variable speed drive
MENU 16: PLC FUNCTIONS
16.05
: Timer 1 value
16.15
: Timer 2 value
16.25
: Timer 3 value
16.35
: Timer 4 value
Adjustment range : 0 to 60.0
Factory setting
: 0
These parameters are used to set the timer delay periods.
The unit depends on the configuration of 16.04, 16.14,
16.24 and 16.34.
16.06
16.08
to
: Not used
16.09
: Timer 1 output destination
16.19
: Timer 2 output destination
16.29
: Timer 3 output destination
16.39
: Timer 4 output destination
Adjustment range : 0.00 to 21.51
: 0.00
Factory setting
These parameters are used to select the destination for the
timer relay outputs.
Only "bit" type parameters can be assigned to these outputs.
If an unsuitable parameter is addressed on an output, the
output will be frozen at 0.
16.10
: Timer 1 inverted output state
16.20
: Timer 2 inverted output state
16.30
: Timer 3 inverted output state
16.40
: Timer 4 inverted output state
Adjustment range : 0 or 1
0 (Disabled) (OFF)
1 (Enabled) (On)
These parameters indicate the state of the inverted output of
the timer relays.
16.16
16.18
to
: Not used
16.26
16.28
to
16.36
16.38
to
16.41
: Latch 1 output
16.51
: Latch 2 output
16.61
: Latch 3 output
16.71
: Latch 4 output
Adjustment range : 0 or 1
These parameters indicate the state of the latching relay
outputs.
3854 en - 03.2008 / b