Emerson Commander SX Advanced User's Manual page 102

Ip66/nema 4x variable speed drive
Table of Contents

Advertisement

CONTROL TECHNIQUES
MENU 11: SERIAL LINK - DRIVE CHARACTERISTICS - MISCELLANEOUS
11.44
: Quick setup menu access
Adjustment range : 0 to 2
Factory setting
: 0
This parameter determines the access level in menu 0, but
only when the drive keypad is used.
LCD
LED
11.44
display
display
0
Level 1
L1
1
Level 2
L2
2
Read only
Loc
The locking procedure using a security code is described in
section 4.3.6 of the installation and commissioning manual
ref. 3840.
11.45
: Motor parameter select
Adjustment range : 0 or 1
Factory setting
: 0
This parameter is used to select the set of parameters corresponding to the characteristics of motor 2.
11.45 = 0 (Motor 1) (Mot1)
1.06
1.07
1.14
2.11
2.21
5.06
5.07
5.08
5.09
5.10
5.11
5.17
5.23
5.24
-
5.25
5.33
5.51
WARNING:
• Switching from one set of motor parameters to the other is performed with the drive disabled.
• When the parameter set for motor 2 is selected, all punctuation marks on the display are lit except for the comma.
102
ADVANCED USER GUIDE
Commander SX
IP66/Nema 4X variable speed drive
Access level
Access to parameters
01 to 10
Access to parameters 01
to 80
All parameters can be
read, but none can be
modified, unless a code
the same as parameter
11.30 is entered at the
time of accessing the
parameter.
11.45 = 1 (Motor 2) (Mot2)
21.01
21.02
21.03
21.04
21.05
21.06
21.07
21.08
21.09
21.10
21.11
21.12
21.13
21.14
21.15
21.24
21.30
21.51
Description
Maximum reference clamp
Minimum reference clamp
Reference selector
Acceleration ramp
Deceleration ramp
Rated frequency
Rated current
Rated speed
Rated voltage
Rated power factor (cos ϕ)
Number of motor poles
Stator resistance
Voltage offset
Transient inductance
Motor 2 parameters active
Stator inductance (Ls)
Motor volts per 1000 rpm (Ke)
q axis inductance
3854 en - 03.2008 / b

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents