Delta Foul V3
16.0
Troubleshooting
Please ensure the installation process has been completed thoroughly and all steps have been followed correctly.
Use the table below to assist with troubleshooting and if problems still occur, please contact the PPS Technical
Department on 01279 757400 from 9:00am - 5:00pm or email info@ppsgroupuk.com.
Water leaking from DC65.
Pump isn't running.
Pump running but not pumping water or discharging
very slow (more than 25 seconds to empty chamber).
Pump is tripping.
High Level Alarm not functioning.
24
Fault
Screws not tightened sufficiently.
Pump hasn't got power - check wiring with reference to
section 12.0 wiring diagram.
Float isn't lifting - check float is free moving and not
catching on chamber - make sure pump is positioned as
diagram 41.
Pump is air locked - make sure there is a level of water to
the top of the pump, remove pump from DC65 and lower
back into water, lift float to activate pump before
reconnecting the DC65.
Discharge pipe is blocked - a drainage company is
required.
Pump is wired incorrectly or not on a separate supply -
refer to section 12.0 wiring diagram.
Refer to the high level alarm installation & operating
instructions.
Cause