OceanStor V3 Series
HyperMetro Feature Guide for File
No.
7
8
9
10
11
12
13
Issue 05 (2018-01-30)
Item
Requirement
Vibration and
l Operating vibration
shock
l Non-operating vibration
l Non-operating shock
Air conditioner
If the temperature in the room exceeds 35°C, you are
recommended to install air conditioners (which can be
restarted after power-off). Do not let the air conditioner blow
directly toward the devices.
Moisture-proof
If the relative humidity is greater than 70%, install the
measures
dehumidifying device, such as the air conditioner with the
dehumidification function or special dehumidifier. Ensure that
the equipment room is protected from water seepage and dew.
Heating
For an environment where the average daily temperature is
lower than 5°C for at least 90 days each year, heating devices
are required. For an environment where the average
temperature is lower than 5°C for 60 to 90 days each year,
heating devices are recommended.
Ventilation and
To ensure smooth ventilation, the cabinet should be at least
heat dissipation
100 cm (39.4 inches) away from the walls and you should
leave a clearance of at least 120 cm (47.28 inches) between
the cabinets. To keep a convective air transfer between the
cabinet and the equipment room, no enclosed space is allowed
in the cabinet. 1 U space should be left above and below each
device.
Dust-proof
For the equipment room near dust sources (such as coal
measures
mines, country roads, or farmland), use double-layer
aluminum alloy windows for proper sealing and an anti-theft
and fireproof door. Separate the devices from the door with a
partition board to avoid dust.
Ground resistance
Less than 10 Ω. The distance between the top of the ground
terminal and the ground should be at least 0.7 m (27.58
inches). In the cold regions, the ground terminal should be
buried under the layer of frozen earth. Periodically monitor
ground resistance to ensure ground effectiveness.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5 Hz to 300 Hz: 1.5 m/s
cycles per axis; 5 Hz to 500 Hz: 0.27 Grms, 3 axes, 10 min
per axis
5 Hz to 20 Hz, PSD: 1.0 m
oct; 3 axes, 30 min per axis
Half sine, 6 ms, 300 m/s
direction
2
, 0.5 oct/min 3 axes, 1 sweep
2
3
/s
; 20 Hz to 200 Hz, –3 dB/
2
, 6 directions, 3 times per