  • Page 3: Mechanical Installation

    AWG 12 wire. Install a switch or circuit breaker nearby; label it clearly as the MP200 unit’s disconnecting mechanism. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03 QS - 1 The Leader In Power Monitoring and Smart Grid Solutions The Leader In Power Monitoring and Smart Grid Solutions...
  • Page 4: Electrical Installation

    IMPORTANT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at www.electroind.com. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03...
  • Page 5 IMPORTANT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at www.electroind.com. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03...
  • Page 6 LOAD Service: Three Phase, 3-Wire Delta Service with 2 CT Connection for Metering 8 Three Phase Loads - MP200-Y IMPORTANT! All CTs must have one side grounded to reduce shock hazard. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03 QS - 4...
  • Page 7 IMPORTANT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at www.electroind.com. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03...
  • Page 8 IMPORTANT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at www.electroind.com. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03...
  • Page 9 Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03 QS - 7 The Leader In Power Monitoring and Smart Grid Solutions The Leader In Power Monitoring and Smart Grid Solutions...
  • Page 10: Communications Settings

    (MP200-S). The second screen is for an MP200 unit with the three phase circuit configura- tion (MP200-Y). The bottom screen is for an MP200 unit with the 2 CT Delta circuit configuration. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03 QS - 8...
  • Page 11: Time Settings

    Note that the hour field uses a 24 hour clock. Update Device: 11. When changes are complete, click the Update button to send a new profile to the MP200 unit. 12. Click Cancel to Exit the screen. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03 QS - 9...
  • Page 12 NOTE: For further details and additional programming screens, refer to the Communicator EXT Software User Manual on the enclosed CD (access the software manual by clicking Help>Contents from the Communicator EXT application’s Title bar). Communicator EXT™ is a trademark of Electro Industries/GaugeTech. Electro Industries/GaugeTech Electro Industries/GaugeTech E166705 V.1.03...