Siemens SIMATIC HMI TP27 Equipment Manual page 208

Hide thumbs Also See for SIMATIC HMI TP27:
Table of Contents

Advertisement

Message
Cause
565
On transferring a global data record, it is established that
not all entries are present.
You have the following options:
1: read the missing entries from the PLC
2: edit the missing entries
3: cancel the Download operation.
566
Data record contains array that does not fit the current
recipe structure.
567, 568
If the message buffer has to be cleared, pending event/
alarm messages also have to be deleted in order to make
space for new message events.
569
Fault on CPI module.
571
S7 system diagnosis/ALARM_S returns error if OP logs
on/off.
572
Query: data record already exists on data medium.
604
Message does not exist.
605
Process link is only configured symbolically.
606
Too many message variables configured.
607
Data type configured does not exist.
613
Data block not available or too short.
622
Configured recipe does not fit in recipe mailbox on PLC
(> 512 data words).
623
Internal error
Screen object for "Send Recipe" is not a recipe type
(fixed by COM TEXT).
624
No recipe entries found.
625
Recipe number does not exist.
626
No setpoints have been configured.
627
Internal error
Configured keyboard block number too high.
628
Recipe does not fit in mailboxes.
TP27, TP37 Equipment Manual
Release 01/00
System Messages
Remedy:
Only returned in the case of data records
that are transferable from one recipe to
another. rel. 3.0 or higher, plastic func-
tions.)
The following question appears:
Save yes/no ?
If you elect to save, the array data is set to
0.
Check configuration. Too many messages
are pending.
CPI no.: defective CPI module
Error:
1 = Voltage too low
2 = Current too high
3 = Temperature too high
4 = Module not present (failed during
operation)
CPU operating system out of date.
If 0 is entered the data record will be over-
written with the new values.
Configure message.
Change configuration and retransfer.
g
g
Create data block of required length on the
PLC.
Reduce configured size of recipe and re-
transfer configuration.
If the fault is not corrected by performing a
restart, please contact the SIMATIC Hot-
line.
Set up area pointers and retransfer configu-
ration.
Reconfigure recipe.
g
p
Correct the block number.
Increase configured size of recipe mailbox
or succeeding recipe mailbox.
C-9