48/50Hc 17-28 Units - Low Voltage Terminal Boards; (Tb A And Tb B); Communication Interface Board (Cib); Central Terminal Board (Ctb) - Carrier 48HC 04-28 Controls, Start-Up, Operation And Troubleshooting

Single package rooftop units with comfortlink controls version 3.x and puron (r-410a) refrigerant
Hide thumbs Also See for 48HC 04-28:
Table of Contents

Advertisement

48/50HC 17-28 Units — Low Voltage Terminal
Boards (TB A and TB B)
There are two terminal boards with 16 terminals each, and ori-
ented one mounted above the other. The front have screw ter-
minals and the back have spade connectors. These terminal
boards provide a connection point for the thermostat or space
sensor and for most field-installed accessories. See Table 33.

Communication Interface Board (CIB)

This circuit board provides a field connection point for unit
communications. The Local Equipment Network (LEN) RJ-11
connector allows a hand-held Navigator to be plugged in to ac-
cess the unit's menus. The Carrier Comfort Network
RJ-11 connector or the CCN screw terminals allow building
communication connections. See Fig. 35.
LEN
CCN
Fig. 35 — Communications Interface Board (CIB)

Central Terminal Board (CTB)

This circuit board is a simple trace board that serves as a junc-
tion point between components and the ComfortLink system. It
is the distribution center for transformer 1's power. The inte-
grated gas controller (IGC), electric heater control, compressor
control, and unit shutdown all feed through this trace board.
See Fig. 36 and Table 34 for the connections through this
board.
Table 33 — Upper and Lower Field Connection Terminal (TB A and TB B) Board Connections (17-28 Size Units)
TERMINAL
TERMINAL
BLOCK
LABEL
C- 2
R- 2
SPT+
SPT-
SPTO
FDWN
Upper
(TB A)
X
G
W1
W2
Y1
Y2
RAT
SAT
HUM
LPWR
COM
Lower
IAQ
(TB B)
SPRH
RMOC
ENTH
R- 2
C- 2
*Point name displayed on the scrolling marquee or Navigator™ display.
®
(CCN)
(+)
(com)
(-)
shield
CCN
DISPLAY
DESCRIPTION
NAME*
Transformer 2 Common
24 VAC power Transformer 2
SPT
Space temperature (T55/56)
SPT
Space temperature (T55/56)
SPTO
Space temperature offset (T56)
FDWN
Fire shutdown switch input
ALRM
Alarm output (normally open)
G
Thermostat G (Fan)
W1
Thermostat W1 (1st stage heat)
W2
Thermostat W2 (2nd stage heat)
Y1
Thermostat Y1 (1st stage cool)
Y2
Thermostat Y2 (2nd stage cool)
RAT
Return Air Temperature Sensor
SAT
Supply Air Temperature Sensor
HUM
Humidistat switch input
Analog Sensor Loop power
(24vdc)
Analog sensor common
IAQ
Indoor air quality sensor
Relative humidity sensor or
SP.RH or OAQ
Outdoor air quality sensor
RM.OC
Remote occupancy switch
ENTH or IAQ.S Outdoor enthalpy switch, or
Indoor air quality switch
24 VAC power Transformer 2
Transformer 2 Common
Fig. 36 — Central Terminal Board (CTB)
SENSOR
LOCATION
space
space
space
supply/return/
space
space
space
space
space
space
space
return duct
Blower or duct
supply/return/
space
return/space
field installed
field installed
economizer, or
return/space
82
TERMINAL
TYPE OF I/O
NUMBER
24 VAC common
1,3,4
24 VAC
13,15,16
10k thermistor
8
10k thermistor
7
10k thermistor
5
24 VAC input
11
24 VAC output
2
24 VAC input
6
24 VAC input
8
24 VAC input
10
24 VAC input
12
24 VAC input
14
10k thermistor
1,3
10k thermistor
5,7
switch input
9
24 VDC
8
Ground
4
4- 20 mA input
6
4-20 mA input
2
24 VAC input
10
24 VAC input
12
24 VAC
15
24 VAC common
16