Carrier 48HC 04-28 Controls, Start-Up, Operation And Troubleshooting page 109

Single package rooftop units with comfortlink controls version 3.x and puron (r-410a) refrigerant
Hide thumbs Also See for 48HC 04-28:
Table of Contents

Advertisement

ITEM
FS.E1
Fan Speed - Free Cool Lo
FS.CL
Fan Speed - Mech Cooling
FS.RH
Fan Speed - Reheat2
S.VFD
SUPPLY FAN VFD CONFIG
N.VLT
VFD1 Nominal Motor Volts
N.AMP
VFD1 Nominal Motor Amps
N.FRQ
VFD1 Nominal Motor Freq
N.RPM
VFD1 Nominal Motor RPM
N.PWR
VFD1 Nominal Motor HPwr
MAX.A
VFD1 Maximum Amps
M.DIR
VFD1 Motor Direction
ACCL
VFD1 Acceleration Time
DECL
VFD1 Deceleration Time
SW.FQ
VFD1 Switching Frequency
COOL
COOLING CONFIGURATION
N.CIR
Number of Circuits
MRT.C
CompressorMin On Time
MOT.C
Compressor Min Off Time
RST.C
Runtime to Reset Strikes
C.DEC
Cool Stage Decrease Time
C.INC
Cool Stage Increase Time
FOD.C
Fan-off Delay, Mech Cool
ALM.N
Alert Each Strike
CA.LO
Circuit A Lockout Temp
CB.LO
Circuit B Lockout Temp
D.CMP
Diagnose Comp Safety
MX.SA
Max Suction Change CirA
MX.SB
Max Suction Change CirB
CS.A1
Current Sensing A1
CS.B1
Current Sensing B1
SAT
Supply Air Temperature
SA.PD
SAT Cool Demand (+) Level
SA.ND
SAT Cool Demand (-) Level
SAT.U
Minimum SAT Upper Level
SAT.L
Minimum SAT Lower Level
SPT
Space Temperature
CL.PD
SPT Cool Demand (+) Level
CL.ND
SPT Cool Demand (-) Level
C.LAG
Cool Thermal Lag Factor
SST
Low Suction Control
SST.O
Suction OK Temperature
SST.1
Low Suction - Level 1
SST.2
Low Suction - Level 2
SST.3
Low Suction - Level 3
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table H — Mode — Configuration (cont)
EXPANSION
0 to 100
60 to 100
65 to 100
0 to 999
0 to 999
10 to 500
50 to 30000
0 to 500
0 to 999
0=FORWARD
1=REVERSE
0 to 1800
0 to 1800
0 to 3
1 or 2
120 to 999
300 to 999
120 to 999
120 to 999
120 to 999
0 to 600
No/Yes
0 to 100F
0 to 100F
Disable/Enable
0 to 100
0 to 100
Disable/Enable
Disable/Enable
0.5 to 10
- 10 to - 0.5
35.0 to 65.0
35.0 to 65.0
0.5 to 5
- 5 to - 0.5
0 to 5
10 to 50
10 to 50
5 to 50
0 to 50
RANGE
UNITS
DEFAULT
%
67
%
67
%
100
230: 208/230v
1ph or 3ph
volts
460: 460v
575: 575v
See VFD Motor
amps
Parameters table
60
See VFD Motor
Parameters table
See VFD Motor
Parameters table
See VFD Motor
amps
Parameters table
0
secs
30
secs
30
2
1 (04- 07)
2 (08- 28)
sec
180
sec
300
sec
300
sec
300
sec
450
30 (04- 05)
sec
75 (06- 28)
Yes
40
0: Low ambient
°F
or Humidimizer
FIOP
40
0: Low ambient
°F
or Humidimizer
FIOP
Enable
4 (04- 06, 17- 28)
PSIG
6 (07- 12)
7 (14)
4 (04- 06, 17- 28)
PSIG
6 (07- 12)
7 (14)
Disable
Disable
^F
1
^F
- 1
53 (04- 14)
°F
56 (17- 28)
42 (04- 14)
°F
46 (17- 28)
^F
1
^F
- 1
1
°F
18
°F
20
°F
15
°F
10
109
CCN TABLE/
CCN POINT
SUB-TABLE
FSPDECO1
FSPDCOOL
FSPDREHT
VFD1NVLT
VFD1NAMP
VFD1NFRQ
VFD1NRPM
VFD1NPWR
VFD1MAXA
VFD1MDIR
VFD1ACCL
VFD1DECL
VFD1SWFQ
COOL_CFG
NUM_CIRC
MIN_ON
MIN_OFF
MIN_ON_S
STAGEDEC
STAGEINC
COOL_FOD
ALM_NOW
OATLCMPA
OATLCMPB
DIAGCOMP
MAXDSSPA
MAXDSSPB
A1_SENSE
B1_SENSE
SAT_POS
SAT_NEG
SATMIN_H
SATMIN_L
DEM_POS
DEM_NEG
COOL_LAG
SSTOK
SSTLEV1
SSTLEV2
SSTLEV3
PAGE
NO.
20
20
20
21
21
21
35
21
21
19
35
21
21
42
42
42
42
42
21
21
43
43
43
43