Carrier 48HC 04-28 Controls, Start-Up, Operation And Troubleshooting page 111

Single package rooftop units with comfortlink controls version 3.x and puron (r-410a) refrigerant
Hide thumbs Also See for 48HC 04-28:
Table of Contents

Advertisement

ITEM
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
DF.DB
Diff Dry Bulb Control
UEFC
Unoccupied Free Cooling
FC.TM
Free Cool PreOcc Time
FC.LO
Free Cool Low Temp Limit
PE.EN
Power Exhaust Installed
PE.1
PE Stage1 Econo Position
PE.2
PE Stage2 Econo Position
PE1C
Power Exhaust Stage1 CFM
PE2C
Power Exhaust Stage2 CFM
IDF.C
Indoor Fan Max Speed CFM
EN.SW
Enthalpy Switch
E.TRV
Economizer Travel Time
E.MXB
Bottom Stage Max Econo
E.MXT
Top Stage Max Econo
LOG.F
Log Title 24 Faults
EC.MD
T24 Econ Move Detect
EC.ST
T24 Econ Move SAT Test
S.CHG
T24 Econ Move SAT Change
E.SOD
T24 Econ RAT-OAT Diff
E.CHD
T24 Heat/Cool End Delay
ET.MN
T24 Test Minimum Pos.
ET.MX
T24 Test Maximum Pos.
AIR.Q
AIR QUALITY CONFIG.
IA.CF
IAQ Analog Input Config
IA.FN
IAQ Analog Fan Config
II.CF
IAQ Switch Input Config
II.FN
IAQ Switch Fan Config
AQ.MN
Econo Min IAQ Position
OVR.P
IAQ Override Position
OA.CF
OAQ Analog Input Config
OAQ.L
OAQ Lockout Limit
AQD.L
AQ Differential Low
AQD.H
AQ Differential High
DF.ON
Fan On AQ Differential
DF.OF
Fan Off AQ Differential
I.4M
IAQ Sensor Value at 4mA
I.20M
IAQ Sensor Value at 20mA
O.4M
OAQ Sensor Value at 4mA
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table H — Mode — Configuration (cont)
EXPANSION
40 to 100
-30 to 50
0=Disable
1=RAT - 0° F
2=RAT - 2° F
3=RAT - 4° F
4=RAT - 6° F
0=Disabled
1=Unoccpied
2=PreOccupancy
1 to 9999
-30 to 70
No/Yes
0 to 100
0 to 100
0 to 15000
0 to 15000
500 to 15000
0=No Switch
1=Normal Open
2=Normal Closed
5 to 300
0 to 100
0 to 100
No/Yes
1 to 10
10 to 20
0 to 5
5 to 20
0 to 60
0 to 50
50 to 100
0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0=Never
1=Occupied
2=Always
0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0=Never
1=Occupied
2=Always
0 to 100
0 to 100
0=No OAQ
1=DCV
2=Lockout OAQ
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
0 to 5000
RANGE
UNITS
DEFAULT
°F
65
°F
0
0=Disable
2
mins
120
F
50
No: no FIOP
Yes: FIOP
%
40
%
75
800 (04- 07)
CFM
1600 (08- 14)
3200 (17- 28)
CFM
0
2000 (04- 07)
CFM
4000 (08- 14)
8000 (17- 28)
0: no FIOP
1: FIOP
secs
150
%
50
25 (03- 14)
%
0 (17- 28)
0: no FIOP
1: FIOP
0
0
0
10
%
0: FIOP EnergyX
%
100
0
600
100
700
600
200
0
2000
0
111
CCN TABLE/
CCN POINT
SUB-TABLE
OATLECLH 23
OATLECLL
DIFFBULB
UEFC_CFG
UEFCTIME
OATLUEFC
PE_ENABL
PE1_POS
PE2_POS 24
PE1_CFM
PE2_CFM
IDF_CFM
ENTHLCFG
ECONOTRV
ECONMAXB
ECONMAXT
T24LOGFL
T24ECMDB
T24ECSTS
T24SATMD
T24RATDF
T24CHDLY
T24TSTMN
T24TSTMX
IAQ_CFG
IAQANCFG
IAQANFAN
IAQINCFG
IAQINFAN
IAQMINP
IAQOVPOS
OAQANCFG
OAQLOCK
DAQ_LOW
DAQ_HIGH
DAQFNON
DAQFNOFF
IAQ_4MA
IAQ_20MA
OAQ_4MA
PAGE
NO.
23
23
24
24
24
24
24
24
10
21
21
22
22
22
22
22
22
24
25
25
26
25
25
25
23
25
25
26
26
24
24
25