Carrier 48HC 04-28 Controls, Start-Up, Operation And Troubleshooting page 129

Single package rooftop units with comfortlink controls version 3.x and puron (r-410a) refrigerant
Hide thumbs Also See for 48HC 04-28:
Table of Contents

Advertisement

APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
MODEL NO.: _____________________________________
SERIAL NO.: _____________________________________
DATE: ___________________________________________
TECHNICIAN: ____________________________________
CONTROL TYPE:
Thermostat/T55 Space Temp./T-56 Space Temp./T-58 Space Temp.
SET POINT
Cooling Occupied: __________________
Heating Occupied: __________________
ITEM
CONFIGURATION
DISP
DISPLAY CONFIGURATION
METR
Metric Display
LANG
Language Selection
PROT
Password Enable
PSWD
Service Password
TEST
Test Display LEDs
UNIT
UNIT CONFIGURATION
S.DLY
Startup Delay
U.CTL
Unit Control Type
T.CTL
Thermostat Control Type
FN.SW
Fan Status Switch
FL.SW
Filter Status Switch
FS.SW
Fire Shutdown Switch
RM.SW
Remote Occupancy Switch
SAT.T
SAT Settling Time
RAT.S
RAT Sensor Installed
RH.S
RH Sensor on OAQ Input
RH.SW
Space Humidity Switch
TCS.C
Temp Cmp Strt Cool Factr
TCS.H
Temp Cmp Strt Heat Factr
I.FAN
INDOOR FAN CONFIG
FTYP
Indoor Fan Type
NSPD
Number of Speeds
OC.FN
Fan On When Occupied
IDF.F
Shut Down on IDF Failure
FS.MX
Supply Fan Maximum Speed
FS.VN
Fan Speed - Ventilation
FS.AQ
Fan Speed - IAQ Override
FS.E1
Fan Speed - Free Cool Lo
FS.CL
Fan Speed - Mech Cooling
FS.RH
Fan Speed - Reheat2
CONTROL SET POINT AND CONFIGURATION LOG
INDICATE UNIT SETTINGS BELOW
Table X — Mode — Configuration
EXPANSION
RANGE
No/Yes
0=English
1=Spanish
2=French
3=Portuguese
Disable/Enable
0000 to 9999
Off/On
10 to 600
2=Thermostat
3=Space Sensor
0=Adaptive
1=1 Stage Y1
2=2 Stage Y1
3=Digital
0=No Switch
1=Normal Open
2=Normal Closed
0=No Switch
1=Normal Open
2=Normal Closed
0=No Switch
1=Normal Open
2=Normal Closed
0=No Switch
1=Normal Open
2=Normal Closed
10 to 900
No/Yes
No/Yes
0=No Switch
1=Normal Open
2=Normal Closed
0 to 60
0 to 60
0=1- SPEED
1=LEN VFD
2, 3, or 7
No/Yes
No/Yes
80 to 100
0 to 100
0 to 100
0 to 100
60 to 100
65 to 100
SOFTWARE VERSIONS
MBB: CESR131504-_ _
ECB: CESR131249-_ _
MARQ: CESR131171-_ _
Unoccupied: __________________
Unoccupied: __________________
UNITS
DEFAULT
SERVICE
CONFIGURATION
DISPLAY
No
0
Enable
1111
(display only, not
Off
in table)
UNIT
sec
30
2
0
0
0
0: no FIOP
1: FIOP
0
sec
240
No
No
0
mins
0
mins
0
AFAN_CFG
0
1: SAV option
2
Yes
Yes
100
%
67
%
100
%
67
%
67
%
100
129
CCN TABLE/
CCN POINT
Sub- TABLE
DISPUNIT
LANGUAGE
PASS_EBL
PASSWORD
DISPTEST
STARTDLY
CTL_TYPE
STATTYPE
FANSTCFG
FILSTCFG
SHTDNCFG
REMOCCFG
SAT_SET
RAT_SENS
RH_OAQ
HUMSTCFG
TCSTCOOL
TCSTHEAT
FAN_TYPE
NUM_SPDS
OCC_FAN
FATALFAN
SPEEDMAX
FSPDVENT
FSPDAQOR
FSPDECO1
FSPDCOOL
FSPDREHT
ENTRY