Carrier 48HC 04-28 Controls, Start-Up, Operation And Troubleshooting page 37

Single package rooftop units with comfortlink controls version 3.x and puron (r-410a) refrigerant
Hide thumbs Also See for 48HC 04-28:
Table of Contents

Advertisement

Table 12 — Configurations - ERV Configurations Read from ComfortLink Controller
SCROLLING
CCN POINT*
MARQUEE
POINT†
OAU_TYPE
OA.TY
OAFANCRV
OA.FC
PEFANCRV
PE.FC
UNOCCRUN
U.RUN
FATALOAU
OAU.F
MODWHEEL
M.WHL
MINOACFM
OA.MN
MINDCVSP
DCV.M
PEX_CTL
PEX.C
EXOFFSET
PE.OF
OAU_BPSP
BP.SP
OATEMPER
OA.TM
OATMPLOC
TM.LO
OATMPSPT
TM.SP
OACFM_K
OAC.K
EXCFM_K
EXC.K
EFB_ENBL
EFBE
* These can be viewed under the CCN Table OAU_CFG with a CCN device.
†These can be viewed under Configuration → OAU on the scrolling marquee or Navigator™ display.
EXPANDED TEXT
0=No OAU
Outdoor Air Unit Type
1=FIOP EXv2
Outside Air Fan Curve
0 to 999
Exhaust Air Fan Curve
0 to 999
OAU Unoccupied
No/Yes
Operation
Shut Down on Fan Failure No/Yes
Modulating Wheel Install
No/Yes
Minimum Outside Air
0 to 32000
CFM
Min DCV Outside Air CFM 0 to 32000
0=offset CFM
Power Exhaust Control
1=BP
Power Exhaust CFM
- 17000 to 17000 CFM –200
Offset
Building Pressure Setpnt
- 0.25 to 0.25
Outside Air Tempering
Disable/Enable
OA Tempring Lockout
0 to 80
Temp
OA Tempring SAT
35 to 80
Setpoint
Outside Air CFM k Factor 0.8 to 1.2
Exhaust Air CFM k Factor 0.8 to 1.2
ERV Fan Boost Enable
No/Yes
RANGE
UNITS
DEFAULT
1: FIOP EXv2
1: 04
2: 05-06
3: 07
4: 08-12
5: 14
6: 17-20
7: 24-28
1: 04, 1ph, and econ
2: 04, 3ph, and econ
3: 04, 1ph, and no econ
4: 04, 3ph, and no econ
5: 05-06 1ph
6: 05-06 3ph
7: 07
8: 08-12
9: 14
10: 17-20 and econ
11: 17-20 and no econ
12: 24-28
NO
YES
NO
375:
04
800:
0506
1000: 07
CFM
2500: 08-12
3000: 14
4000: 17-20
5000: 24-28
100:
04
250:
05-06
600:
07
CFM
1000: 08-12
1500: 14-24
2000: 24-28
0
in H
O 0.05
2
Disable
°F
60
°F
55
1.0
1.0
NO
37
FUNCTION
Defines what kind of OAU is
installed
Determine what outside air fan
curve to use
Determine what exhaust air fan
curve to use
Tells OAU to run in unoccupied
mode
Tells OAU to shut off if one of its
fans fail
Determine if the OAU's wheel is a
modulating one
Sets Design OA CFM for ventilation
Sets absolute minimum OA CFM for
ventilation
Determine how to control the
exhaust fans
Sets offset CFM setpoint of exhaust
based on intake
Sets required building pressure
Determine if there is tempering
heater installed
Sets the outside temp and below to
allow tempering
Sets target supply air temperature
during tempering
Sets outside air curve correction
factor
Sets exhaust air curve correction
factor
Tells RTU to adjust fan speed for
low outside air CFM