Carrier 48HC 04-28 Controls, Start-Up, Operation And Troubleshooting page 131

Single package rooftop units with comfortlink controls version 3.x and puron (r-410a) refrigerant
Hide thumbs Also See for 48HC 04-28:
Table of Contents

Advertisement

APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
ITEM
HMZR
Humidimizer Config
REHT
Humidimizer Equipped
R.DEC
Reheat2 Stage Decr. Time
R.INC
Reheat2 Stage Incr. Time
RA.LO
Reheat2 OAT Limit A
RA.LP
Reheat2 SSP Lo Limit A
RA.HP
Reheat2 SSP Hi Limit A
RB.LO
Reheat2 OAT Limit B
RB.LP
Reheat2 SSP Lo Limit B
RB.HP
Reheat2 SSP Hi Limit B
HEAT
Heating Configuration
HT.TY
Type of Heat Installed
N.HTR
Number of Heat Stages
MRT.H
Heat Minimum On Time
MOT.H
Heat Minimum Off Time
H.DEC
Heat Stage Decrease Time
H.INC
Heat Stage Increase Time
FOD.E
Fan-off Delay, Elect Heat
FOD.G
Fan-off Delay, Gas Heat
HT.LO
Heating Lockout Temp
SAT
SAT.H
SAT Heat Mode Sensing
SAM.L
Maximum SAT Lower Level
SAM.U
Maximum SAT Upper Level
SPT
Space Temperature
HT.PD
SPT Heat Demand (+) Level
HT.ND
SPT Heat Demand (-) Level
H.LAG
Heat Thermal Lag Factor
ECON
Economizer Configuration
EC.EN
Economizer Installed
E.CTL
Economizer Control Type
MP.25
Econ Min at 25% Fanspeed
MP.50
Econ Min at 50% Fanspeed
MP.75
Econ Min at 75% Fanspeed
MP.MX
Econ Min at Max Fanspeed
EC.MX
Econo Cool Max Position
M.ANG
Min Actuator Ctrl Angle
EH.LO
Econo Cool Hi Temp Limit
EL.LO
Econo Cool Lo Temp Limit
Table X — Mode — Configuration (cont)
EXPANSION
RANGE
No/Yes
0 to 999
0 to 999
20 to 70
50 to 100
50 to 100
20 to 70
50 to 100
50 to 100
0=No Heat
1=Gas2=Electric
1 to 2
60 to 999
60 to 999
120 to 999
120 to 999
10 to 600
45 to 600
40 to 125
Disable/Enable
85 to 200
85 to 200
0.5 to 5
- 5 to - 0.5
0 to 5
No/Yes
1=Dig/Position
2=Dig/Command
3=Analog Ctrl
0 to 100
0 to 100
0 to 100
0 to 100
0 to 100
75 to 90
40 to 100
-30 to 50
UNITS
DEFAULT
HMZR_CFG
No
Yes: Humidi-
MiZer FIOP
secs
60
secs
300
°F
40
psig
80
psig
90
°F
50
psig
80
psig
90
HEAT_CFG
0 (50 series with
no electric heat)
1 (48 series)
2 (50 series with
electric heat)
2 (all except
below)
1 (48 series Low
Nox or Single
Phase Unit)
1 (50 series 04-
14 with low heat)
1 (50 series 04-
12 with medium
heat)
1 (50 series 04,
05, with high
heat)
1 (50 series 575v
07- 09, with high
heat)
1 (50 series 460v
07, with high
heat)
sec
120
sec
120
sec
300
sec
450
sec
30
sec
45
°F
75
Disable
°F
140
°F
160
^F
1
^F
-1
1
ECON_CFG
No: no FIOP
Yes: FIOP
1
%
0
%
0
%
0
30
%
0: FIOP EnergyX
%
100
88
°F
65
°F
0
131
CCN TABLE/
CCN POINT
Sub- TABLE
REHEAT
RSTAGDEC
RSTAGINC
OATLRH_A
RHSSPL_A
RHSSPH_A
OATLRH_B
RHSSPL_B
RHSSPH_B
HEATTYPE
NUM_HEAT
HMIN_ON
HMIN_OFF
HSTAGDEC
HSTAGINC
ELEC_FOD
GAS_FOD
OATLHEAT
SAT_HEAT
SATMAX_L
SATMAX_H
HDEM_POS
HDEM_NEG
HEAT_LAG
ECONO
ECON_CTL
MINP_25
MINP_50
MINP_75
MINP_MAX
ECONOMAX
MINANGLE
OATLECLH
OATLECLL
ENTRY