Section 2 Transmission Media and Components
Table 43
Table 43. Electric Current Capability of Flat Cable II Based on Network Length
Network
Length in
Meters
(feet)
Maximum
Electric
Current
(amps)
Figure 13
Figure 13. Electric Current Capability on DeviceNet Power Bus
9ARD000015-600
lists the electric current capability based on the network length.
20
40
80
0
(66)
(131)
(262)
5
5
5
2.75
shows the electric current capability on the DeviceNet Power Bus.
Length of Network in meters (feet)
100
140
200
(328)
(459)
(656)
2.21
1.58
1.11
Flat Cable II
260
300
320
(853)
(984)
(1050)
0.85
0.74
0.69
45