Flat Cable
Table 26. Electrical Characteristics of Data Pair Specification for Flat Cable
Electrical Characteristics
Impedance
Propagation delay
Capacitance between conductors
Capacitive unbalance
DCR - @ 20° C
Attenuation
Table 27. Physical Characteristics of DC Power Specification for Flat Cables
Physical Characteristics
Conductor pair
Insulation diameter
Colors
pair/Twist/ft
Tape shield over pair
36
Section 2 Transmission Media and Components
Specification
120 ohms +/- 10% (at 500 MHz)
1.60 nSec/ft (maximum)
N/A
1.2 pF/ft at 500 kHz (nominal)
ASTMD4566-94
4.9 ohms/1000 ft (maximum)
0.13 db/100 ft @ 125 kHz (maximum)
0.25 db/100 ft @ 250 kHz (maximum)
0.40 db/100 ft @ 500 KHz (maximum)
Specification
Size #16 Copper (minimum); 19 strands
minimum (individually tinned).
0.110 inches (nominal).
Red
Black
N/A
N/A
9ARD000015-600