Thick Cable
Table 11. General Specification for Environmental Characteristics of Thick Cables
Applicable Environmental
Characteristics
Agency Certifications
Flexure
Bend Radius
Operating ambient
temperature
Storage temperature
Pull tension
Connector Compatibility
Topology Compatibility
Table 12
Data Rate
Max
125 kb
250 kb
500 kb
26
According to Federal, State and Local
regulations.
2000 cycles at bend radius, 90 degrees, 2 lb.
Pull force, 15 cycles per minute, Tic Toc or C
track method.
20 x diameter (installation) / 7 x diameter (fixed)
-20° C .. +60° C @ 8 amps; de-rate electric
current linearly to zero @ 80° C.
-40° C .. +85° C.
190 lbs maximum.
Mini, Open.
Trunk, Drop.
lists the topology details of Thick cable.
Table 12. Thick Cable Topology
Cable Distance
(Thick Cable)
500 m (1640 ft)
250 m (820 ft)
100 m (328 ft)
Section 2 Transmission Media and Components
Specification
Trunk
Cumulative
Exchange
Drop
1.0
156 m (512 ft)
1.0
78 m (256 ft)
1.0
39 m (128 ft)
Maximum
Drop
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
9ARD000015-600