Thin Cable
Table 16. Electrical Characteristics of Data Pair Specification for Thin Cable
Electrical Characteristics
Impedance
Propagation delay
Capacitance between conductors
Capacitive unbalance
DCR - @ 20° C
Attenuation
Table 17. Physical Characteristics of DC Power Specification for Thin Cables
Physical Characteristics
Conductor pair
Insulation diameter
Colors
pair/Twist/ft
Tape shield over pair
Table 18. Electrical Characteristic of DC Power Specification for Thin Cable
Electrical Characteristic
DCR - @ 20° C
30
Section 2 Transmission Media and Components
120 Ohms +/- 10% (at 1 MHz)
1.36 nSec/ft (maximum)
12 pF/ ft at 1 kHz (nominal)
1200 pF/1000 ft at 1 kHz (nominal)
28 Ohms/1000 ft (maximum)
0.29 db/100 ft @ 125 kHz (maximum)
0.50 db/100 ft @ 500 kHz (maximum)
0.70 db/100 ft @ 1.00 MHz (maximum)
Specification
Size #22 Copper (minimum); 19 strands
minimum (individually tinned)
0.055 inches (nominal)
Red, Black
5 (approximately)
1.0 mil/ 1.0 mil, Al/Mylar
Al side out w/shorting fold (pull-on applied)
Specification
17.5 Ohms/1000 ft (maximum)
Specification
9ARD000015-600