Flat Cable II
Table 41. Environmental Characteristics of General Specification for Flat Cable II
Applicable Environmental
Characteristics
Agency Certifications
(U.S. and Canada)
Flexure
Bend Radius
Operating ambient temperature -10° C .. +55° C
Storage temperature
Pull tension
Connector Compatibility
Topology Compatibility
Table 42
Data Rate
Max
125 kb
250 kb
500 kb
44
To meet local regulatory agencies.
Specified by vendor (under measurement)
Specified by vendor
-20° C .. +65° C
40 lbs maximum
FLAT II TRUNK CONNECTOR Female and
male
Trunk, Branch
lists the topology details of Flat cable II.
Table 42. Flat Cable II Topology
Cable
Exchange
Distance
(Thick Cable)
265 m (1050 ft)
150 m (574 ft)
75m (213 ft)
Section 2 Transmission Media and Components
Specification
Trunk
Cumulative
Drop
N/A
135 m (511 ft)
N/A
48 m (157 ft)
N/A
35 m (82 ft)
Maximum
Drop
6 m (20 ft)
6 m (20 ft)
6 m (20 ft)
9ARD000015-600