Weights And Dimensions; Zu-A3 Thru -A5 Unit Accessory Weights; Unit 4 Point Load Weight; Unit 6 Point Load Weight - Johnson Controls 20 J ZJ Series Installation Manual

15 - 25 ton 60 hertz
Hide thumbs Also See for 20 J ZJ Series:
Table of Contents

Advertisement

689670-BIM-A-0311
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
LEFT
A
Figure 5: Unit 4 Point Load Weight
Table 2: Weights and Dimensions
Weight (lbs.)
Size
Model
(Tons)
Shipping Operating
-A3
ZU
728
(3)
-A4
ZU
768
(4)
-A5
ZU
869
(5)
Table 3: ZU-A3 thru -A5 Unit Accessory Weights
Unit Accessory
Economizer
Power Exhaust
1
Electric Heat
2
Gas Heat
1. Weight given is for the maximum heater size available (24KW).
2. Weight given is for the maximum number of tube heat exchangers
available (8 tube).
8
FRONT
B
D

Center of Gravity

X
Y
723
40
26
763
40
26
864
40
26
Weight (lbs.)
Shipping
90
40
49
110
A
Figure 6: Unit 6 Point Load Weight
C
Figure 7: Center of Gravity
4 Point Load Location (lbs.)
A
B
C
D
175
143
182
223
185
151
192
235
210
171
217
266
Operating
85
35
49
110
LEFT
C
B
F
Y
X
LEFT
6 Point Load Location (lbs.)
A
B
C
121
105
92
128
111
97
145
126
110
Johnson Controls Unitary Products
FRONT
D
E
FRONT
D
E
F
117
134
154
124
141
162
140
160
184

Advertisement

Table of Contents
loading

This manual is also suitable for:

R-410a

Table of Contents