R-410a variable capacity outdoor split-system air conditioning 2 – 5 tons – 1 phase

Advertisement

Quick Links

INSTALLATION MANUAL

R-410A VARIABLE CAPACITY
OUTDOOR SPLIT-SYSTEM

AIR CONDITIONING

MODELS: 20 SEER
YXV, AC21, AL21 SERIES
2 - 5 TONS - 1 PHASE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Typical Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Alternative Installation Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installation of Vapor Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Outdoor Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Demand Response Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Minimum / Maximum Operating Limit Conditions . . . . . . . . . . . . . . . . .2
Allowable Vertical Linesets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
TEST Mode Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Same Priority Fault Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Status Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Outdoor Display Menu Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
IMPORTANT
It is recommended before starting the system to connect the
thermostat to Wi-Fi using a local network or portable hot-spot
so the thermostat and system receive the latest software
updates to optimize system performance.
CAUTION
!
The EEV is factory installed but shipped in the closed position.
Prior to any brazing, power must be applied to the Indoor Unit. If
installing a coil furnace match or multi-piece air handler system,
the EEV harness must be plugged into the Comm port prior to
applying power to the indoor unit. Allow
open to allow proper nitrogen flow through the coil and lineset. If
you are not able to power the indoor unit before brazing the line
set, a tool to manually open the EEV is available through Source
1 under part number S1-02649686000.
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a nominal sized matching indoor coil plus 15 feet of
field-supplied lines.
Johnson Controls Unitary Products
LIST OF SECTIONS
LIST OF FIGURES
LIST OF TABLES
1 minute
for the EEV to
®
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
OUTDOOR SCREEN OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . 10
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
CHARGING CHARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
START UP SHEET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
System Charging Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Main Outdoor Control and Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Outdoor Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2 Ton Inverter Drive LED Location . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3 & 4 Ton Inverter Drive LED Location . . . . . . . . . . . . . . . . . . . . . . . 19
5 Ton Inverter Drive LED Location . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Wiring Diagram - 2 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Wiring Diagram - 3-5 Ton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Outdoor Control Faults/Status Code Display . . . . . . . . . . . . . . . . . . 12
Inverter Drive Fault/Status Code Display . . . . . . . . . . . . . . . . . . . . . 16
Thermistor Resistance vs Temperature Table . . . . . . . . . . . . . . . . . 21
Sensor Connector Pin Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Low Suction Pressure Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
WARNING
!
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
5284792-UIM-D-1017

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls YXV SERIES

  • Page 1: Table Of Contents

    Sweat connect units are factory charged tractor, installer or service agency. with refrigerant for a nominal sized matching indoor coil plus 15 feet of field-supplied lines. Johnson Controls Unitary Products 5284792-UIM-D-1017...
  • Page 2: Unit Installation

    ° F. The kit part number can be found in the list of accessory kits on the UPGNET web site. Provide adequate structural support for the unit. Johnson Controls Unitary Products...
  • Page 3: Typical Installation Clearances

    5284792-UIM-D-1017 FIGURE 1: Typical Installation Clearances FIGURE 2: Alternative Installation Clearances Johnson Controls Unitary Products...
  • Page 4: Unit Placement

    4. Tape and suspend the refrigerant lines as shown. DO NOT allow See price pages for specific part number for your application. tube metal-to-metal contact. See Figure 3. Johnson Controls Unitary Products...
  • Page 5: Installation Of Vapor Line

    After this con- set, a tool to manually open the EEV is available through Source nection has cooled, remove the nitrogen source from the liquid fit- 1 under part number S1-02649686000. ting service port. Johnson Controls Unitary Products...
  • Page 6: Evacuation

    All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National, Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accordance with the above codes. Johnson Controls Unitary Products...
  • Page 7: System Charge

    Wi-Fi using a local network or portable hot-spot so the thermostat and that the indoor airflow is determined and refrigerant charge added system receive the latest software updates to optimize system perfor- accordingly. mance. Utilize the Hx thermostat to “discover” the system compo- Johnson Controls Unitary Products...
  • Page 8: System Charging Connections

    FIGURE 10: Main Outdoor Control and Display maintenance, service, etc. This may cause damage to the compres- sor and/or other components. Recover and weigh “System Charge” into an appropriate recovery cylinder for any instances requiring evacuation. Johnson Controls Unitary Products...
  • Page 9: Test Mode Option

    Outdoor Display will indicate the most recent system fault and/or event that is stored in memory. The second 5. Suction Temperature system fault will not be displayed, but will be stored in memory. For 6. Suction Pressure example see Table 4. Johnson Controls Unitary Products...
  • Page 10: Same Priority Fault Storage

    2. No Active Call, High Voltage is applied • COMPRESSOR SPEED (RPM) The control will scroll and display * STANDBY * when there are no • OD FAN SPEED (RPM) active calls for compressor operation. • EEV STEP (ID Status) Johnson Controls Unitary Products...
  • Page 11: Outdoor Display Menu Structure

    5 minutes, the outdoor display will Operational Mode: The system will display (Inverter profile and revers- return to General Display Operation. ing valve dependent) unit tonnage when the user selects Operational Mode (AC). Johnson Controls Unitary Products...
  • Page 12: Outdoor Control Faults/Status Code Display

    Correct model Verify the replacement part installed does not INSTALLATION number of drive model number with the list – – match the stored (Solid) ERROR – not installed supplied by Source-1. tonnage in EEPROM HARD LOCKOUT Johnson Controls Unitary Products...
  • Page 13 See Ambient Sensor failure. – (Solid) SENSOR – SHORT Sensor failure. not in lockout yet SUCTION TEMP Suction temperature See Ambient SENSOR – SHORT – See Ambient Sensor failure. – sensor failure (short) (Solid) Sensor failure. SOFT LOCKOUT Johnson Controls Unitary Products...
  • Page 14 WHT and SOFT LOCKOUT BLU/WHT doesn't read between 0.5-4.5 VDC replace sensor. If voltage across WHT and BLU/WHT Bad OD reads between 0.5-4.5 VDC but fault control board still exists, replace OD control board. Johnson Controls Unitary Products...
  • Page 15 See Low Suction Pressure – (Solid) Pressure SOFT LOCKOUT LOW SUCTION See Low Suction Low suction pressure PRESSURE – See Low Suction Pressure – (Solid) Pressure HARD LOCKOUT 1. Refer to Figure 10 for Outdoor Control LED location. Johnson Controls Unitary Products...
  • Page 16: Inverter Drive Fault/Status Code Display

    INVERTER DRIVE Replace drive. damage. Outdoor airflow is Verify proper airflow over the drive heat sink. too low or off. PFC-IGBT PFC-IGBT OVER TEMP – LED604 / LED2 Over Temp INVERTER DRIVE Inverter component Replace drive. damage. Johnson Controls Unitary Products...
  • Page 17 Remove power to system for 2 minutes. Damaged OD Reapply power. If problem remains, Control Board replace OD Control Board. Damaged Remove power to drive for 2 minutes. Reapply Inverter Board power. If problem remains, replace drive. Johnson Controls Unitary Products...
  • Page 18 (Intermediate) Outdoor airflow is too Verify proper airflow over the drive heat sink. low or off. Board Temp High LED 2 Inverter component Replace drive. damage. 1. Refer to Figures 12-14 for LED inverter drive locations. Johnson Controls Unitary Products...
  • Page 19: Ton Inverter Drive Led Location

    5284792-UIM-D-1017 FIGURE 12: 2 Ton Inverter Drive LED Location FIGURE 13: 3 & 4 Ton Inverter Drive LED Location FIGURE 14: 5 Ton Inverter Drive LED Location Johnson Controls Unitary Products...
  • Page 20 Protection Indicating LED (Yellow - 2 or 604) - When the drive is PFC is in operation, the LED will be solid. under protection, the yellow LED will flash. Refer to the fault status and troubleshooting section of this bulletin for more information. Johnson Controls Unitary Products...
  • Page 21: Thermistor Resistance Vs Temperature Table

    280.4 59.0 15714 170.6 1385 282.2 60.8 15000 172.4 1340 284.0 62.6 14323 174.2 1297 285.8 64.4 13681 176.0 1255 287.6 66.2 13071 177.8 1215 289.4 68.0 12493 179.6 1177 291.2 69.8 11942 181.4 1140 293.0 Johnson Controls Unitary Products...
  • Page 22: Instructing The Owner

    If the fault limit value is ever reached for > 5 sec- onds a low suction pressure fault is recognized regardless of a bypass time. TABLE 11: Low Suction Pressure Limits Mode of Operation Trending Limit Fault Limit Cool < 90psi < 5psi Johnson Controls Unitary Products...
  • Page 23: Wiring Diagram

    SEE UNIT V(C) INSTALLATION W(R) OD FAN OD FAN INSTRUCTIONS FOR COMPRESSOR MOTOR CONTROLLER LOW VOLTAGE USE COPPER TERMINATIONS CONDUCTORS ONLY 208-230 VAC 60 Hz 1 PHASE SUPPLY 5295812-UWD-C-0217 FIGURE 15: Wiring Diagram - 2 Ton Johnson Controls Unitary Products...
  • Page 24: Wiring Diagram - 3-5 Ton

    SEE UNIT V(C) INSTALLATION W(R) OD FAN OD FAN INSTRUCTIONS FOR COMPRESSOR MOTOR CONTROLLER LOW VOLTAGE USE COPPER TERMINATIONS CONDUCTORS ONLY 208-230 VAC 60 Hz 1 PHASE SUPPLY 5286847-UWD-C-0217 FIGURE 16: Wiring Diagram - 3-5 Ton Johnson Controls Unitary Products...
  • Page 25: Charging Charts

    Charging chart is for use in Service mode only. Charging chart is for use in Service mode only. Charging chart is for use in Cooling mode only. Charging chart is for use in Cooling mode only. Johnson Controls Unitary Products...
  • Page 26 5284792-UIM-D-1017 NOTES Johnson Controls Unitary Products...
  • Page 27: Start Up Sheet

    Supply air wet bulb temperature Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature Outside air dry bulb temperature Total external static pressure Temperature drop Page 1 of 2 (3/14/17) Johnson Controls Unitary Products...
  • Page 28 Comments and Additional Job Details Page 2 of 2 (3/14/17) Subject to change without notice. Published in U.S.A. 5284792-UIM-D-1017 Copyright © 2017 by Johnson Controls, Inc. All rights reserved. Supersedes: 5284792-UIM-C-0817 York International Corp. 5005 York Drive Norman, OK 73069...