Charging The Unit; Typical Flame; Typical Two Stage Gas Valve; Typical Single Stage Gas Valve - Johnson Controls 20 J ZJ Series Installation Manual

15 - 25 ton 60 hertz
Hide thumbs Also See for 20 J ZJ Series:
Table of Contents

Advertisement

689670-BIM-A-0311
Adjustment Of Temperature Rise
The temperature rise (the difference of temperature between the
return air and the heated air from the furnace) must lie within the
range shown on the CSA rating plate and the data in Table 9.
After the temperature rise has been determined, the CFM can
be calculated as follows:
After about 20 minutes of operation, determine the furnace
temperature rise. Take readings of both the return air and the
heated air in the ducts (about 6 feet from the furnace) where
they will not be affected by radiant heat. Increase the blower
CFM to decrease the temperature rise; decrease the blower
CFM to increase the rise (See SUPPLY AIR DRIVE
ADJUSTMENT).
NOTE: Each gas heat exchanger size has a minimum
allowable CFM. Below this CFM, the limit will open.
Burners/Orifices Inspection/Servicing
Before checking or changing burners, pilot or orifices, CLOSE
MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF ALL
POWER TO THE UNIT.
1.
Open the union fitting just upstream of the unit gas valve
and downstream from the main manual shut-off valve in
the gas supply line.
2.
Remove the screws holding each end of the manifold to the
manifold supports.
3.
Disconnect wiring to the gas valves and spark igniter(s).
Remove the manifold & gas valve assembly. Orifices can
now be inspected and/or replaced.
To service burners, complete step 4.
4.
Remove the heat shield on top of the manifold supports.
Burners are now accessible for inspection and/or
replacement.
NOTE: Reverse the above procedure to replace the
assemblies.
Make sure that burners are level and seat at the rear of the gas
orifice.
GAS
SUPPLY
PIPE
BURNER
BURNER BRACKET
IGNITOR
Figure 29: Typical Flame
50
HEAT EXCHANGER TUBE
BURNER FLAME
(BLUE ONLY)
HIGH & LOW GAS ADJUSTMENT
HI
INLET
PRESSURE
TAP
MATE-N-LOCK
CONNECTORS
Figure 30: Typical Two Stage Gas Valve
ADJUSTMENT
INLET
ELECTRICAL
PRESSURE
TERMINALS
TAP
Figure 31: Typical Single Stage Gas Valve

Charging The Unit

All ZU units use Thermal Expansion Devices. Charge the unit to
10° subcooling.
LO
ON
OFF
OUTLET
PRESSURE
TAP
MV
C
HI
GAS
OUTLET
PRESSURE
TAP
Johnson Controls Unitary Products