1 Short description Microprocessor-controlled burner con- trol system for intermittent operation or continuous operation for controlling and monitoring pneumatically modulating fan-assisted gas burners with speed- regulated or controlled fan and power controller input. Extension modules for: • analogue inputs/outputs • Stepped motor •...
5.1 General information Rated voltage 230 V AC -15 % ... +10 % Frequency 50 ... 60 Hz Fuse MPA 5111 6.3 A slow-blow fuse or 10 A fast-blow fuse, integrated, exchangeable Type of protection IP 20 Ambient temperature 0 °C +60 °C...
5.3 Inputs Designation Safety- Type of input Electrical data Extension Module related 5111 Flame ● Ionisation Threshold value: approx. ● detector 1.2 µA Air pressure ● Switching contact 24V DC / 10 mA ● switch (potential-free) Gas pressure ● Switching contact 24V DC / 10 mA ●...
6 Connection diagram Operation Fault υ MPA5111 Controller chain Mains ~(AC) 230 V Fan motor 50/60 Hz Spark generator Power controller Remote unlocking Safety υ 230 V chain Fuse GDW min. GDW VPS Ionisation pressure switch variable Extension module EMX/Y Display Attention! The designations Y1, Y2 and Y3...
Page 9
Wiring diagram for extension module The extension modules EMX/Y are plug-in printed circuit boards. For the configuration the EM1/1 is the minimum requirement. Old extension modules have a slot for display connection and a slot for PC/laptop connection via VisionBox for system configuration.
GDWVPS is still monitored! ings are limited to 5 in 15 minutes, required that means the automatic system denies further unlockings if the MPA Dungs 7.4.2 Operation with valve check has been unlocked more than 5 times OEM Ex- system within a short time period.
Page 11
The leakage rate corresponds to 0.1 % of the burner's gas consump- tion at maximum burner load, but at least 50 dm /h. A limit value of 200 dm /h is recommended by DUNGS! Safety factor, DUNGS recom- mends triple safety 10 … 68...
Page 12
/ h. The gas = 10mbars - 15 % = 8.5 mbars pressure detector is set to 10 mbars. = 3 (recommendation DUNGS) 20 mbar * 0.44 dm * In (20 mbar / (20 mbar - 12.5 mbar)) = ------------------------------------------------------------------------ * 3600 s/h * 3 = 1.84 s...
Page 13
Test volume of the DUNGS Multiple actuators MB-D ..., MB-ZR..., MB-VEF..., DMV-.., MBC..Type Nominal diameter Test volume Rp / DN DMV-D(LE) 503/11 Rp 3/8 0.03 l DMV-D(LE) 507/11 Rp 3/4 0.10 l DMV-D(LE) 512/11 Rp 1 1/4 0.24 l...
Page 14
Determination of the test volumes for DUNGS Single solenoid valves.../5 Test volumes = volume V1 + V2 + pipeline Nominal diam- output side input side eter Rp / DN direct 0.5 m 1.0 m 1.5 m 2.0 m Rp 3/8 0.01 l...
7.4.3 Operation with reduced pre- Setting for the operation with reduced aeration time pre-aeration time: Under specific circumstances, the a) Pre-aeration time A (P60): 0 or MPA can be started with a reduced pre-aeration time that is always pre-aeration time. For doing this, the required valve tightness test after a regular b) Pre-aeration time B (P61): desired...
7.6 State description MPA 5111 State xx Designation Description The automatic control system is in the initialisation phase Error or initialisation (e.g. reference run of the stepped motor) or an error is ac- tive. If an error is active, the display shows an error message and indicates the current fault (e.g.
Page 17
7.6 State description MPA 5111 State xx Designation Description This time is a second pre-aeration time. Pre-aeration B Contrary to the "Pre-aeration A" state, this state is skipped if the last switch-off of the MPA was a regular switch-off with successful valve tightness test. Moreover, no power failure must have been occurred since the last switch-off.
Page 18
7.6 State description MPA 5111 State xx Designation Description In this mode, the MPA can be modulated via several types Standard mode (see P70 to P76, especially P72). A voluntary switch-off after a defined time can be activated (P70). If this time is set to a maximum of 23 hours and 59 minutes, the MPA is in the intermittent mode.
Page 19
7.6 State description MPA 5111 State xx Designation Description The MPA switches to this state if a lack of gas on the GD- Waiting program WVPS (depending on P46) or an open safety chain has been detected during startup. The MPA remains in this state for a certain waiting time and then carries out another restart test.
8 Parameters 8.1 P1x General parameters Parameter Designation Description Setting / Examples Parameter stick: ac- Indicates if the parameter record Setting 0: tive stick is to be checked or copied, Parameter stick deactivated if necessary, during the restart phase. See also section 8.11 Stick Setting 1: for parameter record and continu- Parameter stick active...
Page 21
Setting 1: No idle state control is carried out. Basically, DUNGS recommends to Otherwise, the LDW is permanent- use the operating mode 0. Excep- ly active. Attention! Ifthe LDW is tions can partly be accepted.
Page 22
8 Parameters 8.1 P1x General parameters Parameter Designation Description Setting / Examples Operating mode The temperature controller can be Setting 0: Temperature controller operated in the following operating The temperature controller is al- modes: ways switched OFF, independently of the hardware input Setting 1: The temperature controller is al- ways switched ON, independently...
Page 23
8 Parameters 8.1 P1x General parameters Parameter Designation Description Setting / Examples Parameter record: This parameter indicates the Record ID record ID defined in the parameter record stick. This allows to distin- guish several parameter record versions of a customer. 0 means "No parameter record found"...
8.2 P2x - Fan rotations has to be indicated in P24. The MPA51 controls the fan by In case of wrong values in P24, the means of PWM signal and evaluates MPA calculates a wrong rotation a hall sensor signal delivered by the speed! fan in form of a rotation speed.
Page 25
8 Parameters 8.2 P2x Fan Parameter Designation Description Setting Fan: KP factor a) For fan control: This factor is only relevant if the fan is controlled! b) For fan regulation: The Kp factor defines the effect of the difference between nominal value and actual value on the regu- lating value.
Page 26
8 Parameters 8.2 P2x Fan Parameter Designation Description Setting Fan: allowed toler- a) For fan control: ance not relevant b) For fan regulation: Here the allowed deviation between the fan speed and the current nomi- nal speed is defined. If the speed has been outside this tolerance range for a longer time period, the MPA is switched off.
8 Parameters 8.3 P3x Stepped motor Parameter Designation Description Setting Stepped motor: Selection Stepped motor type Type Possible types: Parameter value Configuration PWM2 as: Configuration PWM3 as: No stepped motor – reserved – SAD 1.2 or SAD 3.0 (IP54) Standard / delivery position SAD 1.2 or SAD 3.0 (IP54) "changed"...
Page 28
8 Parameters 8.3 P3x Stepped motor Parameter Designation Description Setting Stepped motor: This value defines the highest al- allowed tolerance lowed deviation between the nomi- nal value and the actual value of the determined stepped motor without activating a safety switch-off 27 …...
If this value is inactive, the GD- WVPS input is only evaluated dur- ing the valve test. For the calculation of these parameters or for the settings recommended by DUNGS, see 7.4.2 Operation with valve testing system. 28 … 68...
8 Parameters 8.5 P5x - Additional valve Parameter Designation Description Setting Additional valve: In the state defined here, the output Activation state of the additional valve is activated. Attention! The actual activation can take place with a delay in time! See also P52.
8 Parameters 8.6 P6x - Startup Parameter Designation Description Setting Pre-aeration time A Defines the duration of the pre-aer- ation A. For the difference between pre-aeration A and B, see section "Operation with reduced pre-aera- tion" Pre-aeration time B Defines the duration of the pre-aer- ation B.
8 Parameters 8.7 P7x - Operation Parameter Designation Description Setting Duration Standard Here you can define whether the Typical settings: mode automatic burner control should 0xFFFF = 65535 Continuous op- carry out a voluntary switch-off. If eration / no switch-off. yes, define the operating time (in 1439 = 23h 59 min intermittent op- minutes)
Page 33
8 Parameters 8.7 P7x - Operation Parameter Designation Description Setting Modulation degree: Defines the maximum step width Step width of the of a modulation degree modifica- modification tion without intermediate control. a) By means of relative modifica- tion via the plus or minus input, the nominal value is modified upwards or downwards by the value defined in P73.
8 Parameters 8.8 P8x - Switch-off Parameter Designation Description Setting Regular switch-off: Using this parameter, a transition Transition time time can be activated in which the MPA remains after the failure of the temperature controller / heat re- quest. The flame remains burning. During this time, the MPA moves to the modulation degree defined in P81.
8 Parameters 8.9 P9x - Waiting program Parameter Designation Description Setting Waiting program: Defines the number of restart at- Restart tempts after the errors "Lack of attempts gas on GDWVPS" or "Safety chain open" until the MPA switches to the fault switch-off.
Parameter records Attention! must be generated and created by According to the stick, some DUNGS. parameters are not considered during the adjustment process Attention! (stick with a part quantity of the The parameters in the MPA only parameters).
9 Curve settings/ modulation degree 9.1. Stick and VisionBox The programming of curves is only It is possible to plug in the desired possible using the VisionBox and a parameter record stick or to start parameter record stick! The curves the respective interface of the ap- cannot be processed via the 3 seg- plication software of the connected...
9.2 Definition of terms 9.2.1 Burner capacity Indicates the capacity and/or heat produced by the burner. Typically, the capacity is indicated in kWh. 9.2.2 Modulation degree A specific combination of nominal Attention! Normally, there is a difference be- value for the fan, stepped motor 0 % (100 %) do not comply neces- tween the modulation degree and position and nominal value for PWM...
10 Error overview MPA 51xx Error Internal Error description Possible cause of the error error 10.1 Errors from processor 2 No bus connection to processor 1 ? TWI bus connection blocked by an de- Display ● fective external bus user, for example a flashes defective VisionBox or ..
10 Error overview MPA 51xx Error Internal Error description Possible cause of the error error ERROR _PARAMETER _RECORD_STICK _ ? A parameter could not be copied from 0x4C BLOCK_ADJUSTMENT the stick, for ex. because the variable lim- its in the MPA were confined. ERROR_PARAMETER_RECORD_STICK_IN- ? The entered password is not suitable for 0x4d...
Page 43
10 Error overview MPA 51xx Error Internal Error description Possible cause of the error error ERROR_NO_FLAME_DURING_SZA ? Ionisation electrode incorrectly set ? Ignition electrodes incorrectly set ? Insulated lines of the ignition electrodes or the ionisation electrode defective ? Pneumatic composite incorrectly set / Incorrect gas type 0xA7 ? Gas valves do not open the gas flow...
11 Display unit 11.1 Overview display modes Mode Active Operational status display in normal operation if no error is active Error display if the automatic burner control is in the fault switch-off phase Info display by pressing the key combination (+ and ↵) in state 1 or 35 Service display by pressing the key combination...
11.6 Error display Error display An error message is automatically displayed as soon as the automatic system goes to the fault lock ▶ system. ▶ The error that has occurred last is displayed. Automatic activation if a fault is active As long as the Plus key is kept depressed, the state number is displayed...
11.7 Information display Info display ▶ The info display is activated out of the operational status display. Using the info display, information on the current counter reading such as ▶ start counter and permanent runtime meter can be called. ▶ This operating mode is left after a timeout of 20 s if no key is pressed within this time period.
11.8 Service display Service display ▶ The service display is activated out of the operational status display. ▶ The service display can only be activated in the burner mode. ▶ A heat request must be active on the temperature controller input. ▶...
11.9 Parameterisation display Parameterisation display The parameterisation display can only be activated when the standby mode on the operational ▶ state indicator is active. ▶ The parameters which cannot be changed due to the access level are only displayed. Activation of the parameterisation display by simultaneous pressing of the keys Previous parameter Next parameter...
11.9 Parameterisation display cancel Parameter type U16 confirmation Set the thousands confirmation Value Value Set the ones reduction cancel reduction Value Value increase increase Value in P1 correctly saved Code input confirmation Code input High Byte Low Byte Value Value reduction reduction cancel...
11.10 Reset display Reset display ▶ The reset display is activated out of the operational status display. The error memory, the access levels, resettable runtime meter and start counter can be reset by ▶ means of the reset display. ▶ This operating mode is left after a timeout of 20 s if no key is pressed within this time period.
Page 53
Value Value reduction reduction confirmation Value increase Value increase confirmation cancel Switches to the operation display Correct password Incorrect password Flashing display until the level 30 s elapsed Error, change is confirmed by means of without level flashing display Value the reset key switching for 5 s...
11.11 Error memory display Display of the error memory ▶ The display of the error memory is used to call the last ten errors. ▶ The error that has occurred last is displayed. ▶ The error memory display is activated out of the operational status display. ▶...
11.12 Password entry parameter record stick Password input for parameter stick If the parameter values of the plugged-in parameter stick do not comply with the stored parameter ▶ values of the automatic system, a password must be entered before starting the automatic system. Then, the parameter values are copied.
13 Flame detector The following flame detectors are approved by DUNGS and can be recommended for use in connection with the MPA51xx: Manufacturer Designation Type Output signal Reaction Certificate Continuous time operation Ionisation Ionisation Ionisation < 1 s electrode BST solutions...
14 Stepped motor 14.1 Overview of the possible stepped motor types SAD 15 SAD 1.2 WG SAD 1.5 SAD 1.2 SAD 3.0 WG SAD 3.0 (IP 40) SAD 10 WG 14.2 Reference point "Standard" The rotation ranges are indicated 0° 0°...
14.4 Mathematical angle positions of the stepped motor position 0° or The mathematical angle position is 90° for the respective stepped mo- indicated in the view from the bottom tor type is indicated in the following 90° on the driven shaft as shown in the table: 0°...
14.5 Wiring diagram SAD15 Power supply PIN designation in the SAD 15 230 V mains power supply or MPA output 6 Signal lines SAD15 PIN designation in the SAD 15 230 V mains power supply or MPA output 6 not used not used Connection SAD15 EA SA...
14.6 Power supply of the stepped motors Stepped motor 230 V (L1) 24 V by means of a sepa- 24 V via MPA5111 Mains power supply rate power supply unit SAD 1.2 X (> 7W) SAD 1.2 WG X (> 7.5W) SAD 1.5 X (>...
15 Time diagram MPA51xx Parameter Time State number Safety chain Watchdog Alarm Temperature controller Additional valve *4 Ignition Fan relay PWM1 (fan) PWM2 (for ex. analogue 0...10 V) ● PWM3 (for ex. analogue 4... 20 mA) ● Stepped motor ● Flame (ionisation) LDW *1 GDW min.
Page 64
*5) The GDW VPS is monitored during the goes to the fault switch-off. The waiting pro- valve test. Additionally, the parameter P46 gram state is triggered by a lack of gas or an can define whether the minimum pressure open safety chain. monitoring via GDWVPS during operation between state 17 and state 25 is active or not.
Page 65
Appendix A Versions and variants Variant Version SAP device SAP SW P1 Stick type for VisionBox MPA5111 V1.0 251446 D 251547 _ 51 1 V1.1 251446 E 251547 A 51 2 Changes from V1.0 to V1.1 1. The V1.1 version corresponds to VDE EN60335-1 section 30 of 2007.
Page 66
Appendix B Parameter overview Name DUNGS Einheit Bedeutung Einstellwerte Zugriffs- Aus- ebene lieferung PARAMETER_STICK_AKTIV Parameterstick: aktiv ANZAHL_WIEDERANLAUFVER- Wiederanlaufver- SUCHE suche ANZAHL_WIEDERANLAUFVER- Wiederanlaufver- SUCHE_NACH_FEHLER_ suche nach fehlend- KEINE_FLAMME_WAEHREND_ er Flammenbildung ANZAHL_WIEDERANLAUFVER- Wiederanlaufver- SUCHE_NACH_FEHLER_ suche nach Flam- FLAMMENABRISS_IM_BE- menabriss TRIEB BETRIEBSART_LDW LDW: Betriebsart...
Page 67
Name DUNGS Einheit Bedeutung Einstellwerte Zugriffs- Aus- ebene lieferung ZUSATZVENTIL_EINSCHALT- State Zusatzventil: Ein- STATE schaltstate ZUSATZVENTIL_AUSSCHALT- State Zusatzventil: Auss- STATE chaltstate ZUSATZVENTIL_EIN- 1/16 s Zusatzventil: Ein- 65535 OEM SCHALTVERZOEGERUNG schaltverzögerung ZUSATZVENTIL_AUSS- 1/16 s Zusatzventil: Auss- 65535 OEM CHALTVERZOEGERUNG chaltverzögerung DAUER_VORBELUEFTUNG_A 1/16 s Vorbelüftungszeit A...