Speed Filter - Vexta aStep AS Series Operating Manual

Table of Contents

Advertisement

Speed filter

Use the speed-filter selection switch "V.FIL" to select the filter time constant that determines the
motor's response to pulse input.
The switch provides a selection of 16 levels ranging between "0" and "F."
When a larger value is selected, it will reduce shock when the motor is started and stopped, and
will minimize low-speed vibration.
An unnecessarily large filter time constant, however, will smooth out the motor movement
further but with a reduced ability to synchronize to the pulse input and extended settling time
when stopping. Select an optimal value to fit the load and application.
Factory setting
[6]: 1.20 ms
CURRENT
The dial settings and corresponding levels of filter time constants are as follows:
Dial setting
Filter time [ms]
0
None
1
0.12
2
0.16
3
0.27
4
0.41
0.82
5
6
1.20
7
1.60
8
2.70
9
4.10
A
8.20
B
12.0
C
16.0
D
27.0
E
41.0
F
82.0
When the speed-filter selection switch is set to "0"
V.FIL
Speed-filter selection switch
When the speed-filter selection switch is set to "E"
Command speed
Motor speed
END output
Command speed
Motor speed
END output
45