Internal Dip Switches; Internal Jumpers - Siemens NK8222 Installation, Function & Configuration

Ethernet port for a single subsystem, ethernet port, cei interface for a single subsystem, ethernet port for a single subsystem, modbus gateway
Table of Contents

Advertisement

NK822x Structure and Functions
4.2

Internal DIP switches

4.3

Internal jumpers

18
Building Technologies
Fire Safety & Security Products
The internal DIP switches enable a download session via FTP using a default IP
address.
Note: There are two internal DIP switches, but only DIP switch 2 is presently used.
Internal switch
DIP switch 1
DIP switch 2
Tab.3.
Internal DIP switches
The internal jumpers (see Fig. 2) are used for:
 JP3: When closed, it disables the box tamper alarm;
 JP6: When closed, it enables the LON termination resistor (100Ω) for a doubly
terminated bus topology.
DIP-Switches
Reset button
Fig. 2
NK822x internal DIP switch and jumpers
Functions
Not presently used.
Default mode/network access:
If DIP-switch 2 is ON, an FTP connection occurs by default on the
Ethernet at the default IP address 192.168.9.41.
JP6: Enable LON resistor
048_DMS_NK8000_ICC_MP4.40_A6V10062437_a_en.doc
JP3: Disable tamper or
connect to external
tamper
Tamper switch
CN1
CN3
CN4
06.2011