Internal Dip Switches; Internal Jumpers - Siemens NK8222 Installation, Function & Configuration

Ethernet port for a single subsystem, ethernet port, cei interface for a single subsystem, ethernet port for a single subsystem, modbus gateway
Table of Contents

Advertisement

NK823x Structure and Functions
5.2

Internal DIP switches

5.3

Internal jumpers

S101: DIP-Switches
24
Building Technologies
Fire Safety & Security Products
The four LED's on the right side are, from top to bottom:
Front panel LED (right
Com1
Com2
Com3
Com4
Tab.6.
LED functions on the front panel, right side
The internal DIP switches (S101) enable a download session via FTP using a de-
fault IP address.
Internal switch
DIP switch 1
DIP switch 2
Tab.7.
Internal DIP switches
The internal jumpers (see Fig. 8) are used for:
 X115: When closed, it disables the box tamper alarm.
S1: Reset button
X2
X1
Fig. 8
NK823x internal DIP switch and jumpers (NKM8001-A2 mainboard)
Functions
Status Com1
Red:
Status Com2
Green:
Status Com3
Status Com4
Functions
Default mode/network access:
If DIP-switch 1 is ON, an FTP connection occurs by default on the
Ethernet 1 at the default IP address 192.168.9.41.
Default mode/network access:
If DIP-switch 2 is ON, an FTP connection occurs by default on the
Ethernet 2 at the default IP address 192.168.10.41.
S2: Tamper switch
X102
X101
X3
048_DMS_NK8000_ICC_MP4.40_A6V10062437_a_en.doc
RX
TX
X103
X104
X105
06.2011
X111