2.2

Interactions

2.3

What has been changed in MP4.40 configuration tools

Building Technologies
Fire Safety & Security Products
Local interactions
Interactions are possible between the subsystems connected to each NK82xx unit
and the locally connected I/O modules. Incoming messages can trigger one or
more command messages to other subsystems. Thanks to the high reliability of the
NK82xx units, these interactions are more secure than reactions and sequences
programmed on the management station level.
Network-wide interactions
Network-wide interactions via BACnet/IP are possible between subsystems con-
nected to any NK8225/NK8232/NK8235 unit on the automation level network.
Note: Incoming messages can be combined with the logical operators AND, OR,
XOR, and NOT.
Interaction configuration is performed at management station level via an easy-to-
use tool, and then downloaded to the NK82xx.
 For details on interactions, see the DMS8000 Network, Fire & Intrusion Connec-
tivity Guide (document no.A6V10062425).
Note: NK8000 units are not certified as part of an EN54-2 fire detection system.
Therefore, NK8000 interactions should only be used in applications where they
are not in conflict with EN54 standards or national guidelines or regulations (e.g.
not for common control of remote transmission devices).
Control units supported
 CS11 AlgoRex Fire control units
 FC700A Fire control units
 SIGMASYS/D100 Fire control units
 STT20/STT2410 Fire control units
 XLS FireFinder control units
 CS6 Guarto Intrusion control units (NK822x only)
 SI410 Intrunet (formerly Sintony) Intrusion control units
 DF8000/CF9000 I/O modules
 MK7022 Cerloop Interface
 CS1115 Fire control units
 FC330A Fire control units
 FS20 Sinteso Fire control units
 FS720 Cerberus Pro Fire control units
Here is the list of modifications included in this version for new functions and soft-
ware improvements.
Section, Page
Modifications
Various
Support of BACnet protocol on NK8232, NK8235, NK8237
Support of locally connected DF8000 I/O modules
Interactions with FS20/FS720 (require new NK823x main-
board)
048_DMS_NK8000_ICC_MP4.40_A6V10062437_a_en.doc
Introduction
11
06.2011