Commissioning - Promation Engineering P1.A Series Installation & Operation Manual

Hide thumbs Also See for P1.A Series:
Table of Contents

Advertisement

Commissioning

This procedure will assume that the actuator is installed correctly both mechanically and electrically with correct power at
terminals marked 4 & 5 and control signal at terminals marked 6 & 7.
1. Apply the correct supply power to the actuator.
NOTE - Power is measured at terminals marked 4 & 5 on the actuator.
The POWER (Yellow) LED will illuminate whenever power is on.
2. Test Full CW and CCW Positions for Direct Acting Mode (DIP 6 set to OFF)
2.A Generate a MAXIMUM control signal at the PLC or signal generator.
I.
The actuator OUTPUT shaft will drive to the full CCW position while the INDICATOR/cam shaft rotates to the
full CW position (as viewed from ABOVE the actuator).
II. If this is NOT the correct stop position, refer to Adjusting the actuator CCW position instructions for CAM 1 on
Page 7 in this document.
2.B Generate a MINIMUM control signal at the PLC or signal generator.
The actuator OUTPUT shaft will drive to the full CW position while the INDICATOR/cam shaft rotates to the
I.
full CCW position (as viewed from ABOVE the actuator).
II. If this is NOT the correct stop position, refer to Adjusting the actuator CW position instructions for CAM 2 on
Page 7 in this document.
3. Test Full CW and CCW Positions for Reverse Acting Mode (DIP 6 set to ON)
3.A Generate a MAXIMUM control signal at the PLC or signal generator.
I.
The actuator OUTPUT shaft will drive to the full CW position while the INDICATOR/cam shaft rotates to the
full CCW position (as viewed from ABOVE the actuator).
II. If this is NOT the correct stop position, refer to Adjusting the actuator CW position instructions for CAM 2 on
Page 7 in this document.
3.B Generate a MINIMUM control signal at the PLC or signal generator.
I.
The actuator OUTPUT shaft will drive to the full CCW position while the INDICATOR/cam shaft rotates to the
full CW position (as viewed from ABOVE the actuator).
II. If this is NOT the correct stop position, refer to Adjusting the actuator CCW position instructions for CAM 1 on
Page 7 in this document.
NOTE- The feedback signal generator shows the 4-20mA or 2-10vdc position output at terminals marked 11 (-) & 12 (+).
IF THE END OF TRAVEL CAMS ARE ADJUSTED, THEN THE ACTUATOR MUST BE RECALIBRATED. REFER TO
CALIBRATION PROCEDURE ON PAGE 12.
Page 11 of 13 P1.A-24V-ACDC Standard Proportional Series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents