SECTION 12: Motor Protective Devices - 50/60 Hz

12.3 Mounting And Installation

Mount the Pentek
Motor Protector in a convenient
®
location in or near the motor control panel. If the location
is wet or dusty, then the Pentek Motor Protector should
be mounted in a NEMA 3R, 4, or 12 enclosure.

12.4 Wiring Connections

1. Connect one line from the fused disconnect to the
Motor protector's "L1 IN" terminal. Run a wire from
the "L1 OUT" terminal to the other in-line controls
such as a pressure or float switch. See Figure 10-1.
2. Connect the other line from the fused disconnect to
Motor Protector "L2 IN" terminal. Run a wire from the
"L2 OUT" terminal to the other in-line controls such
as pressure or float switches. See Figure 12-1.
NOTICE: The Motor Protector may not detect a dead head
(blocked pipe) condition on applications where the pump
is undersized for a given motor or flow restrictors are
used on high stage pumps or low yield wells.
L2
GND
L1
RUN
LIGHT
Fused
Disconnect
L1
L2
GND
Alternate Pressure Switch
Location When Rapid Cycle
Protection is not needed
Figure 12-1: SPP233 Standard Control Box Connection
Calibration/Settings
NOTICE: Calibrate the Motor Protector during normal
pumping conditions.
1. Turn the RESTART DELAY / CALIBRATION adjustment
fully counter-clockwise to the "CAL." position.
2. Apply power to the Motor Protector. The pump motor
should be running at this point.
3. The Motor Protector is being calibrated when the
CAL. LIGHT turns on (approximately 5 seconds).
Within 10 seconds, proceed to step 4.
4. Set the RESTART DELAY / CALIBRATION adjustment
to the desired Restart Delay (Dry Well Recovery Time).
If you leave the RESTART DELAY / CALIBRATION
adjustment in the "CAL." position, the unit will trip
off and stay off. Turn the adjustment out of the "CAL."
position to start the pump.
88
100
150
50
2
225
CAL
RESET
CAL
LIGHT
Submersible Pump Protector
L1 OUT
L2 IN
L1 IN
L2 OUT
Standard 3-Wire
Pressure
Control Box
Switch
1/3 to 3 HP
5201
GND
L2
L1
Fused
Disconnect
L1
L2
GND
Figure 12-2: "Plus" Control Box Connection for
SPP233
L2
GND
L1
Fused
Disconnect
L1
L2
GND
Alternate Pressure Switch
Location When Rapid Cycle
Protection is not needed
Figure 12-3: 2-Wire Connection for SPP233
Motor
Manual Reset Mode: If the RESTART DELAY /
CALIBRATION adjustment is set to "RESET", the Motor
protector is in Manual Reset mode. After the Motor
Protector shuts down due to a voltage or load problem,
the RESTART DELAY / CALIBRATION adjustment must be
rotated out of the "RESET" position to restart the pump.
NOTICE: Any restart delay can be by-passed by rotating
the RESTART DELAY / CALIBRATION adjustment to
the "RESET" position and back to the desired Restart
Delay setting.
Rapid Cycling Protection: Rapid cycling is defined as
more than four restarts in a 60 second period. The Motor
Protector will lockout upon detecting a rapid cycling
condition until power is removed and re-applied to the
L1 IN and L2 IN terminals. See Diagnostics Table for
instructions to diagnose a rapid cycling fault.
100
50
150
2
225
CAL
RESET
RUN
CAL
LIGHT
LIGHT
Submersible Pump Protector
L1 OUT
L2 IN
L1 IN
L2 OUT
4" Plus 3-Wire
Control Box
Pressure
Switch
SW
SW
100
150
50
2
225
CAL
RESET
RUN
LIGHT
Submersible Pump Protector
L1 OUT
L2 IN
L1 IN
L2 OUT
Pressure
Switch
Motor
CAL
LIGHT
5204