SECTION 9: PPC Series 50/60 Hz Variable Frequency Drives
9.6
Pentek
Assistant
®
Table 9-6: PPC3 Parameters Changed Relative to PID Control Defaults
Parameter Code
1002 Ext2 Commands
1102 EXT1/EXT2 Sel
1301 Minimum AI1
1601 Run Enable
1805 DO Signal
1806 DO On Delay
1806 DO On Delay
1807 DO Off Delay
2001 Minimum Speed
2001 Minimum Speed
2002 Maximum Speed
2202 Accel Time 1
2202 Accel Time 1
3001 AI<Min
3003 External Fault 1
3006 Mot Therm Time
3006 Mot Therm Time
3007 Mot Load Curve
3007 Mot Load Curve
3013 Underload Function
3014 Underload Time
3022 AI2 Fault Limi
3201 Superv 1 Param
3202 SuperV 1 Lim Lo
3203 SuperV 1 Lim Hi
9.6.1 Description of Information
by the Pentek Assistant
9905 Motor Nom Voltage: This is the nominal voltage
stated on the motor nameplate. If the motor is rated
for operation at multiple voltages, select the voltage
nearest the utility voltage. Ensure the motor connections
correspond to the voltage selected.
9906 Motor Nom Current: This is the nominal current
found on the motor nameplate. Do not use service
factor amps.
9907 Motor Nom Freq: This is the nominal frequency
found on the motor nameplate.
9908 Motor Nominal Speed: This is the nominal speed
found on the motor nameplate. Use the number on the
motor nameplate. Do not enter 3600, 1800, etc.
9909 Motor Nom Power: This is the nominal horsepower
found on the motor nameplate. Do not include service
factor unless the service factor is greater than 1.15.
Pentek Code
Keypad
EXT2
20%
Not Sel
Superv1 Over
10 Seconds (Above Ground)
60 Seconds (Submersible)
2 sec
0 (Above Ground)
User Defined (Submersible)
Sync
5 sec (Above Ground)
1 sec(Submersible)
Fault
DI5
500 sec (Above Ground)
350 sec (Submersible)
100% (Above Ground)
112% (Submersible)
Fault
10 sec
10%
Output Freq
per 9907
per 9907
Required
Parameter Code
3401 Signal 1 Param
3405 Output 1 Unit
3408 Signal 2 Param
3412 Output 2 Unit
3415 Signal 3 Param
3419 Output 3 Unit
4001 Gain
4002 Integration Time
4006 Units
4010 Set Point Sel
4022 Sleep Selection
4024 PID Sleep Delta
4027 PID Param Set
4101 Gain
4102 Integration Time
4106 Units
4109 100% value
4110 Set Point Sel
4111 Internal Setpoint
4122 Sleep Selection
4123 PID Sleep Level
4124 PID Sleep Delay
4125 Wake-Up Deviation
2001 Min Speed (Required for Subs only): This is the
minimum speed the motor is allowed to run. This
minimum is set to prevent damage to the motor thrust
bearings. Refer to motor literature to determine setting.
4011 Internal Setpoint: This is the pressure that the
system will maintain.
4009 100% Value: This is the full scale reading of the
transducer. The 100% Value of a 200PSI transducer
is 200PSI.
4023 PID Sleep Level: Operation below this rpm will
cause the drive to stop. Must never be below the shut-off
head RPM.
4025 Wake-Up Dev: This is the pressure drop that will
trigger the drive to restart. For example, if the set point is
60 PSI and the Wake-Up Deviation is 10 PSI, the drive will
restart at 50 PSI.
Pentek Code
Current
A
Speed
RPM
PID 1 FBK
PSI
1.0
1.0
PSI
Internal
Internal
10 sec
DI3
1.0
1.0 Sec
PSI
Per 4009
Internal
Per 4011
Internal
Per 4023
10 sec
Per 4025
71